175
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
M1OvrLoadTime (31.11) and M1RecoveryTime (31.12)
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B8-9 reserved
B10
MainsLowVolt
A111 3
mains low (under-) voltage, PwrLossTrip (30.21), UNetMin1 (30.22), UNetMin2
(30.23)
B11
reserved
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B12
COM8Com
A113 4
SDCS-COM-8
communication loss
B13
ArmCurDev
A114 3
armature current deviation
B14
TachoRange
A115 4
Overflow of AITacho input or M1OvrSpeed (30.16) has been changed
B15
reserved
Int. Scaling: 1 == 1
Type: I
Volatile:
Y
9.07 AlarmWord2 (alarm word 2)
Alarm word 2:
Bit
Alarm text
Alarm code
Comment
and alarm level
B0
ArmCurRipple
A117 4
armature current ripple, CurRippleMode (30.18, CurRippleLim (30.19)
B1-3 reserved
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B4
AutotuneFail
A121 4
autotuning failure, Diagnosis (9.11)
B5
reserved
B6
FaultSuppres
A123 4
at least one fault message is mask
B7
SpeedScale
A124 4
speed scaling out of range, M1SpeedScale (50.01) and M1BaseSpeed (99.04),
the parameter causing the alarm can be identified in Diagnosis (9.11)
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B8
SpeedFb
A125 4
selected motor: speed feedback, M1SpeedFbSel (50.03), SpeedFbFltMode
(30.36), SpeedFbFltSel (30.17)
B9
ExternalDI
A126 4
external alarm via binary input, ExtAlarmSel (30.32)
B10
AIRange
A127 4
analog input range, AI Mon4mA(30.29)
B11
FieldBusCom
A128 4
fieldbus communication loss, ComLossCtrl (30.28)
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B12
ParRestored
A129 4
The parameters found in flash are invalid at power-up (checksum fault). The
parameters were restored from the parameter backup.
B13
LocalCmdLoss
A130 4
local command loss, LocalLossCtrl (30.27)
B14
ParAdded
A131 4
A new firmware with a different amount of parameters was downloaded. The
new parameters are set to their default values. The parameters causing the
alarm can be identified in Diagnosis (9.11).
B15
ParConflict
A132 4
parameter setting conflict, the parameter causing the alarm can be identified in
Diagnosis (9.11)
Int. Scaling: 1 == 1
Type: I
Volatile:
Y
9.08 AlarmWord3 (alarm word 3)
Alarm word 3:
Bit
Alarm text
Alarm code
Comment
and alarm level
B0
RetainInv
A133 -
retain data invalid
B1
ParComp
A134 4
parameter compatibility, the parameter causing the alarm can be identified in
Diagnosis (9.11)
B2
ParUpDwnLoad
A135 4
The checksum verification failed during up- or download of parameters. Please
try again.
B3
NoAPTaskTime
A136 4
AP task for not set in TimeLevSel (83.04)
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B4
SpeedNotZero
A137 1
Re-start of drive is not possible. Speed zero -see M1ZeroSpeedLim (20.03) -
has not been reached. In case of a trip set On = Run = 0 to reset the alarm.
B5
Off2FieldBus
A138 1
Off2 (Emergency Off / Coast Stop) pending via fieldbus, Off2 (10.08)
B6
Off3FieldBus
A139 1
Off3 (E-stop) pending via fieldbus, E Stop (10.09)
B7
IllgFieldBus
A140 4
the fieldbus parameters in group 51 (fieldbus) are not set according to the
fieldbus adapter or the device has not been selected
------------------------------------------------------------------------------------------------------------------------------------------------------------------
B8
COM8FwVer
A141 4
invalid combination of SDCS-CON-F firmware and SDCS-COM-8 firmware
Содержание DCS550 Series
Страница 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Страница 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...