211
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
23.09 WinWidthNeg (negative window width)
Negative speed limit for the window control, when the speed error (
∆
n = n
ref
- n
act
) is negative.
Internally limited from:
rpm
to
rpm
20000
32767
*
)
29
.
2
(
20000
32767
*
)
29
.
2
(
−
Int. Scaling: (2.29)
Type: I
Volatile:
N
-10000
10000
0
rp
m
23.10 SpeedStep (speed step)
SpeedStep (23.10) is added to the speed error (
∆
n) at the speed controller’s input. The given min./max.
values are limited by M1SpeedMin (20.02) and M1SpeedMax (20.02).
Internally limited from:
rpm
to
rpm
20000
32767
*
)
29
.
2
(
20000
32767
*
)
29
.
2
(
−
Note:
Since this speed offset is added after the speed ramp, it must be set to zero prior to stopping the drive.
Int. Scaling: (2.29)
Type: SI
Volatile:
Y
-10000
10000
0
rp
m
23.11 SpeedErrFilt2 (2
nd
filter for
∆
n)
Speed error (
∆
n) filter time 2. There are three different filters for actual speed and speed error (
∆
n):
−
SpeedFiltTime (50.06) is filtering the actual speed and should be used for filter times smaller than 30 ms.
−
SpeedErrFilt (23.06) and SpeedErrFilt2 (23.11) are filtering the speed error (
∆
n) and should be used for
filter times greater than 30 ms. It is recommended to set SpeedErrFilt (23.06) = SpeedErrFilt2 (23.11).
Int. Scaling: 1 == 1 ms
Type: I
Volatile:
N
0
10000
0
ms
23.12 Unused
23.13 AuxSpeedRef (auxiliary speed reference)
Auxiliary speed reference input for the speed control of the drive. Can be connected to SpeedRefUsed (2.17)
via:
−
Ref1Mux (11.02) and Ref1Sel (11.03) or
−
Ref2Mux (11.12) and Ref2Sel (11.06)
Internally limited from:
rpm
to
rpm
20000
32767
*
)
29
.
2
(
20000
32767
*
)
29
.
2
(
−
Int. Scaling: (2.29)
Type: SI
Volatile:
Y
-10000
10000
0
rp
m
23.14 Unused
23.15 DirectSpeedRef (direct speed reference)
Direct speed input is connected to SpeedRef3 (2.02) by means of AuxCtrlWord2 (7.03) bit 10 = 1 and
replaces the speed ramp output.
Internally limited from:
rpm
to
rpm
20000
32767
*
)
29
.
2
(
20000
32767
*
)
29
.
2
(
−
Note:
Since this speed offset is added after the speed ramp, it must be set to zero prior to stopping the drive.
Int. Scaling: (2.29)
Type: SI
Volatile:
Y
-10000
10000
0
rp
m
23.16 SpeedRefScale (speed reference scaling)
Speed reference scaling. After SpeedRef3 (2.02) and before SpeedRef4 (2.18).
Int. Scaling: 100 == 1 % Type: I
Volatile:
N
-325
325
1
00
%
Group 24: Speed control
The Speed controller is based on a PID algorithm and is presented as follows:
(
)
(
)
29
.
2
*
%
100
*
1
1
1
*
*
)
(
)
(
)
(
n
s
act
s
ref
s
ref
T
TF
s
TD
s
TiS
s
n
n
KpS
T
+
+
+
−
=
with:
−
T
ref
= torque reference
−
KpS = proportional gain [KpS (24.03)]
−
N
ref
= speed reference
−
N
act
= speed actual
−
TiS = Integration time [TiS (24.09)]
Содержание DCS550 Series
Страница 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Страница 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...