30
Electrical installation
3ADW000379R0501 DCS550 Manual e e
Fan connection for DCS550:
Cabling
Thermal overload and short-circuit protection
The drive protects itself and the input and motor cables against thermal overload when the cables are
dimensioned according to the nominal current of the drive.
Power cables
Dimension the mains and motor cables according to local regulations. The cables must:
1. be able to carry the DCS550 load current,
2. be rated for at least 60°C (140°F),
3. fulfill short-circuit protection,
4. be rated according permissible touch voltage appearing under fault conditions (so that the fault point
voltage will not rise too high when an earth fault occurs) and
5. be screened according to safety regulations.
Mains cable (AC line cable) short-circuit protection
Always protect the input cable with fuses. Size the fuses according to local safety regulations, appropriate
input voltage and the rated current of the drive, see chapter
High-speed semiconductor fuses provide short-circuit protection, but do not provide thermal overload
protection.
1
2
3
X52:
4
5
L
N
1
2
3
X52:
4
5
L
N
115 V
AC
M
~
1
2
3
X52:
M
~
4
5
M55
M56
M
~
1
2
3
X52:
M
~
4
5
M55
M56
M
~
M
~
M57
M58
M55
M
~
1
2
3
4
5
X52:
L
N
L
N
1
2
3
X52:
4
5
L
N
230 V
AC
230 V
AC
1
2
3
X52:
4
5
L
N
115 V
AC
J
M55
M
~
X19:
SDCS-PIN-F
F4
F3
F2, F3
F1
SA_550_002_fan_a.ai
only 230 V
AC
Configuration 4
Configuration 3
Configuration 2
Configuration 1
Terminals are located on top of the converter housing
Содержание DCS550 Series
Страница 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Страница 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...