210
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
23.03 FixedSpeed2 (fixed speed 2)
FixedSpeed2 (23.03) is specifying a constant speed reference and overrides SpeedRef2 (2.01) at the speed
ramps input. It can be released by Jog2 (10.18) or MainCtrlWord (7.01) bit 9. The ramp times are set with
JogAccTime (22.12) and JogDecTime (22.13).
Internally limited from:
rpm
to
rpm
20000
32767
*
)
29
.
2
(
20000
32767
*
)
29
.
2
(
−
Int. Scaling: (2.29)
Type: SI
Volatile:
N
-1
0000
10000
0
rp
m
23.04 SpeedCorr (speed correction)
The SpeedCorr (23.04) is added to the ramped reference SpeedRef3 (2.02).
Internally limited from:
rpm
to
rpm
20000
32767
*
)
29
.
2
(
20000
32767
*
)
29
.
2
(
−
Note:
Since this speed offset is added after the speed ramp, it must be set to zero prior to stopping the drive.
Int. Scaling: (2.29)
Type: SI
Volatile:
Y
-10000
10000
0
rp
m
23.05 SpeedShare (speed sharing)
Scaling factor SpeedRefUsed (2.17). Before speed ramp.
Int. Scaling: 10 == 1 %
Type: SI
Volatile:
N
-400
400
100
%
23.06 SpeedErrFilt (filter for
∆
n)
Speed error (
∆
n) filter time 1. There are three different filters for actual speed and speed error (
∆
n):
−
SpeedFiltTime (50.06) is filtering the actual speed and should be used for filter times smaller than 30 ms.
−
SpeedErrFilt (23.06) and SpeedErrFilt2 (23.11) are filtering the speed error (
∆
n) and should be used for
filter times greater than 30 ms. It is recommended to set SpeedErrFilt (23.06) = SpeedErrFilt2 (23.11).
Int. Scaling: 1 == 1 ms
Type: I
Volatile:
N
0
10000
0
ms
23.07 Unused
Idea of Window Control:
The idea of the Window Control is to block the speed controller as long as the speed error (
∆
n) remains within the window
set by WinWidthPos (23.08) and WinWidthNeg (23.09). This allows the external torque reference - TorqRef1 (2.08) - to
affect the process directly. If the speed error (
∆
n) exceeds the programmed window, the speed controller becomes active
and influences the process by means of TorqRef2 (2.09). To release window control set TorqSel (26.01) = Add and
AuxCtrlWord (7.02) bit 7 = 1.
This function could be called over/underspeed protection in torque control mode:
Note:
to open a window with a width of 100 rpm set WinWidthPos (23.08) = 50 rpm and WinWidthNeg (23.09) = -50 rpm.
23.08 WinWidthPos (positive window width)
Positive speed limit for the window control, when the speed error (
∆
n = n
ref
- n
act
) is positive.
Internally limited from:
rpm
to
rpm
20000
32767
*
)
29
.
2
(
20000
32767
*
)
29
.
2
(
−
Int. Scaling: (2.29)
Type: I
Volatile:
N
-10000
10000
0
rp
m
Содержание DCS550 Series
Страница 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Страница 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...