199
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
Group 16: System control inputs
16.01 Unused
16.02 ParLock (parameter lock)
The user can lock all parameters by means of ParLock (16.02) and SysPassCode (16.03). To lock parameters
set SysPassCode (16.03) to the desired value and change ParLock (16.02) from Open to Locked. Unlocking
of parameters is only possible if the proper pass code (the value that was present during locking) is used. To
open parameters set SysPassCode (16.03) to the proper value and change ParLock (16.02) from Locked to
Open.
After the parameters are locked or opened the value in SysPassCode (16.03) is automatically changed to 0:
0 = Open
parameter change possible, default
1 = Locked parameter change not possible
Int. Scaling: 1 == 1
Type: C
Volatile:
N
O
pen
Loc
k
ed
O
pen
-
16.03 SysPassCode (system pass code)
The SysPassCode (16.03) is a number between 1 and 30,000 to lock all parameters by means of ParLock
(16.02). After using Open or Locked SysPassCode (16.03) is automatically set back to zero.
Attention:
Do not forget the pass code!
Int. Scaling: 1 == 1
Type: I
Volatile:
Y
0
30000
0
-
16.04 LocLock (local lock)
Local control can be disabled by setting LocLock (16.04) to True. If LocLock (16.04) is released in local
control, it becomes valid after the next changeover to remote control. No pass code is required to change
LocLock (16.04):
0 = False
local control released, default
1 = True
local control blocked
Int. Scaling: 1 == 1
Type: C
Volatile:
N
F
a
lse
T
ru
e
F
a
lse
-
16.05 Unused
16.06 ParApplSave (save parameters)
If parameters are written to cyclic, e.g. from an overriding control, they are only stored in the RAM and not in
the flash. By means of ParApplSave (16.06), all parameter values are saved from the RAM into the flash:
0 = Done
parameters are saved, default
1 = Save
saves the actual used parameters into the flash
After the action is finished ParApplSave (16.06) is changed back to Done. This will take max. 1 second.
Note:
Do not use the parameter save function unnecessarily
Note:
Parameters changed by DCS Control Panel or commissioning tools are immediately saved into the flash.
Int. Scaling: 1 == 1
Type: C
Volatile:
Y
D
one
Sa
v
e
D
one
-
16.07 - 16.10 Unused
16.11 SetSystemTime (set the drive’s system time)
Sets the time of the converter in minutes. The system time can be either set by means of SetSystemTime
(16.11) or via the DCS Control Panel.
Int. Scaling: 1 == 1 min
Type: I
Volatile:
Y
0
64000
0
m
in
16.12 - 16.13 Unused
16.14 ToolLinkConfig (tool link configuration)
The communication speed of the serial communication for the commissioning tool and the application program
tool can be selected with ToolLinkConfig (16.14):
0 = 9600
9600 Baud
1 = 19200
19200 Baud
2 = 38400
38400 Baud, default
3 = 57600
57600 Baud
4 = 115200
115200 Baud
If ToolLinkConfig (16.14) is changed its new value is taken over after the next power up.
Int. Scaling: 1 == 1
Type: C
Volatile:
N
9600
11520
0
38400
Содержание DCS550 Series
Страница 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Страница 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...