261
Signal and parameter list
3ADW000379R0501 DCS550 Manual e e
Signal / Parameter name
m
in.
ma
x.
def
.
uni
t
92.10 DsetXplus7Val1 (data set X+7 value 1)
Data set 8 value 1 (interval: 3 ms).
Default setting of 904 equals FaultWord4 (9.04).
Int. Scaling: 1 == 1
Type: I
Volatile:
N
0
9999
904
-
Group 97: Measurements
97.01 TypeCode (type code)
TypeCode (97.01) is preset in the factory and is write protected. It identifies the drives current-, voltage-,
temperature measurement and its quadrant type. To un-protect the type code set ServiceMode (99.06) =
SetTypeCode. The change of the type code is immediately taken over and ServiceMode (99.06) is
automatically set back to NormalMode:
0 = None
no type code set
1 = S01-0020-05
type code, see table
to
xxx = S02-1000-05 type code, see table
The drive’s basic type code: DCS550-AAX-YYYY-ZZ
Product family:
DCS550
Type:
AA
= S0 Standard converter modules
Bridge type:
X
= 1
Single bridge (2-Q)
= 2
2 anti parallel bridges (4-Q)
Module type:
YYYY
=
Rated DC current
Rated AC voltage:
ZZ
= 05 230 V
AC
- 525 V
AC
Int. Scaling: 1 == 1
Type: C
Volatile:
Y
N
one
S0
1
-520
3
-05
fac
tor
y
pr
es
e
t v
al
ue
-
97.02 - 97.03 Unused
97.04 S MaxBrdgTemp (set: maximum bridge temperature)
Adjustment of the converters heat sink temperature tripping level in degree centigrade:
0 °C =
take value from TypeCode (97.01), default
1 °C to 149 °C =
take value from S MaxBrdgTemp (97.04)
150 °C =
the temperature supervision is inactive, if S MaxBrdgTemp (97.04) is set to 150 °C
This value overrides the type code and is immediately visible in MaxBridgeTemp (4.17).
Int. Scaling: 1 == 1 °C
Type: I
Volatile:
N
0
150
0
°C
97.05 - 97.06 Unused
97.07 S BlockBridge2 (set: block bridge 2)
Bridge 2 can be blocked:
0 = Auto
operation mode is taken from TypeCode (97.01), default
1 = BlockBridge2
block bridge 2 (== 2-Q operation), for e.g. 2-Q rebuild kits
2 = RelBridge2
release bridge 2 (== 4-Q operation), for e.g. 4-Q rebuild kits
This value overrides the type code and is immediately visible in QuadrantType (4.15).
Int. Scaling: 1 == 1
Type: C
Volatile:
N
Au
to
R
el
B
ri
dg
e2
Au
to
-
97.08 Unused
97.09 MainsCompTime (mains compensation time)
Mains voltage compensation filter time constant. Is used for the mains voltage compensation at the current
controller output.
Setting MainsCompTime (97.09) to 1000 ms disables the mains voltage compensation.
Int. Scaling: 1 == 1 ms
Type: I
Volatile:
N
0
1000
10
ms
97.10 - 97.12 Unused
Содержание DCS550 Series
Страница 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Страница 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...