7.6 Communication failure between PROFIsafe-based laser scanner, PLC, and
controller
Description
The ProfiNet LED on the laser scanner is not lit up, indicating that the profinet
communication between the laser scanner, PLC, and OmniCore controller fails to
be set up. However, the cable connection is properly connected and necessary
parameters are correctly set during the laser scanner configuration.
This issue may occur when PROFIsafe-based laser scanner(s) is connected.
Consequences
Communication fails to be set up between the laser scanner, PLC, and OmniCore.
The safety separation function with the laser scanner cannot be applied.
Possible causes
The firewall for the ProfiNet network is disabled.
Recommended actions
1 Open RobotStudio.
2 In the
Controller
tab page, choose
Communication
from the
Configuration
group.
3 Select
Firewall Manager
in the
Type
pane.
4 Set
Enable on Public Network
to
Yes
for the network service
ProfiNet
.
1066
Product manual - CRB 15000
3HAC077389-001 Revision: L
© Copyright 2021 - 2023 ABB. All rights reserved.
7 Troubleshooting
7.6 Communication failure between PROFIsafe-based laser scanner, PLC, and controller
Содержание CRB 15000
Страница 1: ...ROBOTICS Product manual CRB 15000 ...
Страница 2: ...Trace back information Workspace 23B version a17 Checked in 2023 06 29 Skribenta version 5 5 019 ...
Страница 8: ...This page is intentionally left blank ...
Страница 16: ...This page is intentionally left blank ...
Страница 38: ...This page is intentionally left blank ...
Страница 54: ...This page is intentionally left blank ...
Страница 182: ...This page is intentionally left blank ...
Страница 200: ...This page is intentionally left blank ...
Страница 1058: ...This page is intentionally left blank ...
Страница 1076: ...This page is intentionally left blank ...
Страница 1095: ......