Modifications reserved
Page 31/94
Interfacing
Each UPS cabinet is provided with customer interface ports (also called communication ports) which
provides information about the UPS (single units) or the UPS system (parallel system).
The customer interface is composed by (see also the figure 12 at the end of this section):
•
Slot for optional Modem card
•
Slot for optional SNMP card
•
PC / laptop connection
JD1 (RS232 Sub D9/female) or USB
•
Status LED’s
1 red LED and 1 green LED
•
Graphical display connection JR3 (RJ 45)
•
Multidrop configuration
SW2 (DIP-SWITCH)
•
Multidrop connection
JR2 (RJ 45)
•
UPS inputs
X3 (Phoenix terminals)
•
12VDC source
X3 5/6 (Phoenix terminals)
•
UPS outputs, dry ports
X2 (Phoenix terminals)
•
Interlock Function
X1 1/2 (Phoenix terminals)
•
Multi-Cabinet Configuration
SW1-6 (DIP-SWITCH)
•
Sync input
X1 Sync (Phoenix terminals)
•
Parallel BUS connector
JD8 (Sub D25/female)
5.1
Smart port JD1 on each frame (Serial RS 232 / Sub D9 / Male)
The SMART PORT JD1 located on the customer interface board (see figure 10 above, detail 9) RS
232 serial port that allows the UPS Module to be connected to a computer. The connector is a
standard D-Type, 9-pin, male. When installed the optional SMART PORT, the software WAVEMON
allows the computer to monitor the mains voltage and the UPS status continuously.
In the event of any changes the computer terminal will display a message.
(For details see our Monitoring Package:
WAVEMON
).
The figure 11 shows how to connect a PC to the UPS with different Sub-D connectors.
Interface Cable (UPS End)
Interface cable (Computer End)
(9-Pin, D-Type Male)
(9-Pin, D-Type Female)
Connects to UPS
Connects to
JD1
Computer
Figure 11: Connector Cable - PC Serial Port with 9-Pin Connection
1
2
3
9
.
.
5
1
2
3
9
.
.
5
Содержание Conceptpower DPA 500
Страница 1: ... Copyright 2017 ABB All rights reserved Operating manual Conceptpower DPA 500 100 500 kW ...
Страница 2: ......
Страница 79: ... Copyright 2017 ABB All rights reserved Appendix A Xtra VFI 3 ph UPS products ...
Страница 88: ...Modifications reserved Page 88 94 Attachments Technical data sheet ...
Страница 90: ......
Страница 91: ... Copyright 2017 ABB All rights reserved Technical data sheet Conceptpower DPA 500 100 500 kW ...