Modifications reserved
Page 9/25
4
Output characteristics
Conceptpower DPA 500
Values
Unit
Power, rated:
500
100
kW
AC power distribution system: TN-S, TN-C, TN-C-S, TT
available phases
3
-
neutral available
yes
-
Voltage (steady state, r.m.s.), rated
3x380/220V+N
3x400/230V+N
3x415/240V+N
VAC
Variation in normal mode / battery mode
± 1.5 / ± 1.5
%
Total harmonic distortion (THDu), 100% load, normal mode:
Linear
< 2.0
%
Non-linear
(acc. to IEC 62040-3)
< 4.0 %
%
Total harmonic distortion (THDu), 100% load, battery mode:
Linear
< 2.0
%
Non-linear
(acc. to IEC 62040-3)
< 4.0 %
%
Voltage unbalance and phase displacement,
100% load
unbalance
0
°
Voltage transient and recovery time, 100% step load:
Linear
± 4
%
Non-linear
(acc. to IEC 62040-3)
± 4
%
Transfer normal mode --> battery mode
0
%
Frequency (steady-state), rated:
50 / 60 (selectable)
Hz
Variation in normal mode
(frq. Synchronized with mains)
± 2 / ± 4
%
Variation in battery mode
(free-running)
± 0.1
%
Max synch phase error (referred to a 360° cycle)
<2
°
Max slew-rate
1
Hz/s
Nominal current (In), r.m.s. rated:
725
145
A
Overload on inverter
0.5 @ 150% load,
5 @ 125% load,
20 @ 110% load
min
Fault clearing capability normal mode and battery mode
(100ms)
1711 (2.36xIn)
348 (2.4xIn)
A
Load power factor, rated
1
-
Displacement
(permissible lead-lag range)
(all range) 0
%, s
Double conversion efficiency in normal mode, linear load:
Содержание Conceptpower DPA 500
Страница 1: ... Copyright 2017 ABB All rights reserved Operating manual Conceptpower DPA 500 100 500 kW ...
Страница 2: ......
Страница 79: ... Copyright 2017 ABB All rights reserved Appendix A Xtra VFI 3 ph UPS products ...
Страница 88: ...Modifications reserved Page 88 94 Attachments Technical data sheet ...
Страница 90: ......
Страница 91: ... Copyright 2017 ABB All rights reserved Technical data sheet Conceptpower DPA 500 100 500 kW ...