6
User interface - communication
STANDARD ITEMS
System Display
7” touchscreen display (one per frame)
DPA display (or module display)
2 x 20 character LCD display (one per module)
MIMIC diagram
LED-indicator, 5x green/red LEDS (one per module)
RS232 on Sub-D9 port
RS232 on USB port
For monitoring and integration in network management
Customer Interfaces:
Inputs DRY PORT
1 Remote Shut down [EMERGENCY OFF (Normally closed)]
1 GEN-ON (Normally open)
1 Programmable Customer’s Inputs (Normally open)
1 Temp. Sensor for Battery Control
Customer Interfaces : Outputs
DRY PORT
6 voltage free contacts
For remote signaling and automatic computer shutdown
RS485 on RJ45 port
Remote monitoring system with remote panel (graphical display)
RS485 on RJ45 port
For multidrop purpose
Slot for SNMP
SNMP card
For monitoring and integration in
network management
Slot for SNMP
6.1
System display
The user-friendly touchscreen graphical display the system level, offers the opportunity of directly
monitoring the system status as well as measurements and access to the EVENT LOG. The graphical
display additionally provides status and measurements of each single module within the system. All
other commands must be performed on the DPA display. With both displays in place (module and
system level), the UPS offers full user friendliness without making compromises on robustness
.
Содержание Conceptpower DPA 500
Страница 1: ... Copyright 2017 ABB All rights reserved Operating manual Conceptpower DPA 500 100 500 kW ...
Страница 2: ......
Страница 79: ... Copyright 2017 ABB All rights reserved Appendix A Xtra VFI 3 ph UPS products ...
Страница 88: ...Modifications reserved Page 88 94 Attachments Technical data sheet ...
Страница 90: ......
Страница 91: ... Copyright 2017 ABB All rights reserved Technical data sheet Conceptpower DPA 500 100 500 kW ...