background image

26

User Manual

Rittal PMC UPS 6kVA

Germany

Rittal GmbH & Co. KG
Auf dem Stützelberg
D-35745 Herborn
Tel.: ++49-27 72-5 05-0
Fax: ++49-27 72-5 05-23 19
Internet: www.rittal.de

Summary of Contents for PMC

Page 1: ...26 User Manual Rittal PMC UPS 6kVA Germany Rittal GmbH Co KG Auf dem Stützelberg D 35745 Herborn Tel 49 27 72 5 05 0 Fax 49 27 72 5 05 23 19 Internet www rittal de ...

Page 2: ...nected unit RITTAL PMC UPS 6KVA 36 4 3 Battery extension 40 5 Troubleshooting 42 6 Maintenance 45 6 1 Operation 45 6 2 Storage 45 7 Technical data 46 7 1 Electrical specifications 46 7 2 Typical stored energy time Battery mode 47 7 3 Dimensions and weights 47 7 4 Operating environment 47 7 5 Port connectors 48 7 5 1 RS232 interface 48 7 5 2 Relay interface Option 48 8 Appendix 26 ...

Page 3: ...he stabiliser to RITTAL PMC UPS 6KVA 37 Figure 4 Connection diagram for RITTAL PMC UPS 6KVA 38 Figure 5 Connection of battery extensions to RITTAL PMC UPS 6kVA 40 Figure 6 Circuit diagram of relay interface 49 Figure 7 Front and back view of RITTAL PMC UPS 6KVA 51 Figure 8 Back view of battery extension for RITTAL PMC UPS 6KVA 52 ...

Page 4: ...ing current from the socket outlet to direct current This direct current charges the batteries and powers the inverter On the basis of this DC voltage the inverter generates a sinusoidal AC voltage which permanently supplies the loads Computers and periphery are thus powered entirely independently of the mains voltage In the event of power failure the maintenance free batteries power the inverter ...

Page 5: ...bsolutely dry before being installed Please allow an acclimatisation time of at least two hours Do not install the UPS system near water or in damp environments Do not install the UPS system where it would be exposed to direct sunlight or near heat Do not block off ventilation openings in the UPS system s housing Installation Please note the special installation aspects for the permanently connect...

Page 6: ...rations since this would cancel the protective earthing of the UPS system and of all connected loads The UPS system features its own internal current source batteries The UPS output sockets may be electrically live even if the UPS system is not connected to the building wiring socket outlet In order to fully disconnect the UPS system first press the Standby switch then disconnect the mains lead or...

Page 7: ...input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no voltage is present Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below and any other measures necessary when working with batteries remove wristwatches rings and other metal objects use only tools w...

Page 8: ...1 Front Panel Figure 1 Operating and display panel Switch Function ON Switch 1 Turn on UPS system By pressing the ON Switch I the UPS system is turned on 2 Deactivate acoustic alarm By pressing this switch an acoustic alarm can be deactivated ...

Page 9: ...ED The orange coloured BATTERY LED lights up when the mains power supply has failed and the inverter is being powered by the batteries BYPASS LED The orange coloured BYPASS LED lights up when the UPS system is supplying voltage provided by the mains power supply system via the bypass INVERTER LED The green INVERTER LED lights up if the inverter of the UPS is operating and supplying the UPS output ...

Page 10: ...35 ...

Page 11: ...th LED 95 100 2 In the case of battery operation the LEDs indicate the capacity of the batteries 1st LED 1 35 2nd LED 35 55 3rd LED 55 75 4th LED 75 95 5th LED 95 100 3 2 Back Panel Slide buttons on the back panel allow selection of the outgoing voltage of the UPS system This can be changed only when the UPS system is switched off Figure 2 Slide buttons to select output voltage ...

Page 12: ...he electrical wiring please note the nominal amperage of your incoming feeder UPS 6000 VA are not suitable for 16 A sub distribution boards 1 Inspect the packaging carton and its contents for damage Please inform the transport agency immediately should you find signs of damage Please keep the packaging in a safe place for future use 2 Fit the supplied stabiliser as shown in the illustration below ...

Page 13: ...so that the castors are not contacting the ground 3 Please ensure that the incoming feeder is isolated and secured to prevent it from being switched back on again Set the I P and the O P switch on the back panel to position OFF 4 Connect the UPS system to the mains at the screw terminals as shown in the diagram below ...

Page 14: ...system e g laser printers Do not connect domestic appliances to the UPS system 6 Set the I P switch on the back panel to position ON Note Load capacity LEDs first light up simultaneously then one after the other After a few seconds the INVERTER LED lights up and the BYPASS LED turns off 7 Fully charge the batteries of the UPS system by leaving the UPS system connected to the mains for 1 2 hours Yo...

Page 15: ...ghts up after 10 seconds The BYPASS LED then goes out and the ventilation system switches on The UPS system is now operating correctly 10 Test the function of the UPS system by either pressing the On button I or disconnecting the input of the UPS system from the power supply Caution The output sockets of the UPS system may still be electrically live even if the power supply system has been disconn...

Page 16: ... to the UPS system proceed as shown below 1 Disconnect the UPS system from the mains power supply and the load from the UPS system 2 Connect the battery extensions to the UPS system with the included cables according to the following instructions Figure 5 Connection of battery extensions to RITTAL PMC UPS 6KVA ...

Page 17: ... system can now operate normally Note Operating the system with external battery extensions prolongs charging to 24 hours with one battery extension and to 48 hours with two battery extensions after total discharge ...

Page 18: ...em is connected to mains power supply I P switch has been disconnected Set the I P switch to ON BATTERY LED blinks Battery voltage 12VDC per unit When battery voltage 12VDC per unit then clear warning signal LINE LED blinks and BATTERY LED lights up Input power and or frequency are out of tolerance Check input power source and inform dealer if necessary LINE LED and BYPASS LED light up even though...

Page 19: ...pply available I P switch disconnected Set the I P switch to ON If the problem persists please inform your dealer FAULT LED lights up warning tone once a second Overload Reduce number of users at UPS output FAULT LED lights up permanent warning tone UPS mistake Notify dealer Emergency supply period shorter than nominal value Batteries not fully charged batteries defective Charge the batteries for ...

Page 20: ...45 Please have the following information at hand before calling the After Sales Service Department 1 Model number serial number 2 Date on which the problem occurred 3 Detailed description of the problem ...

Page 21: ... been exceeded the batteries must be exchanged In this case please contact your dealer 6 2 Storage If the batteries are to be stored in temperate climatic zones they should be charged every three months for 1 2 hours see Chapter Installation and Start Up You should shorten the charging intervals to two months at locations subject to high temperatures ...

Page 22: ...A 4200 W Voltage 220 230 240 VAC 0 5 synchronized Frequency 50 60 Hz 0 5 free wheeling Wave form Sinusoidal BATTERIES Number and type 20 x12V 7Ah The units bear the CE mark and comply with the following standards limit value class B EN 60950 1992 8 EN 50091 1 1994 4 prEN 50091 3 1994 4 EN 50081 1 1992 2 EN 50082 1 1992 2 IEC 801 2 Level 4 IEC 801 3 Level 3 IEC 801 4 Level 4 IEC 801 5 Level 2 ...

Page 23: ...A 2 battery extensions 60 141 7 3 Dimensions and weights Model Dimensions W x H x D mm Net Weight kg Gross Weight kg RITTAL PMC UPS 6KVA 260 x 710 x 555 91 107 Battery extension for RITTAL PMC UPS 6KVA 260 x 710 x 555 125 145 7 4 Operating environment Temperature 10 C to 40 C Installation height 1500 m 0 C to 35 C Installation height 1500 m to 3000 m Relative humidity 20 to 90 no condensation ...

Page 24: ...witched off and the UPS system to be switched off There are various software packages for implementing these functions Please consult your dealer for further details 7 5 1 RS232 interface The 9 pin Sub D connector socket makes an RS232 interface available Description of the PIN assignment Pin 2 RXD received data 3 TXD transmitted data 5 GND ground 7 5 2 Relay interface Option The 9 pin Sub D conne...

Page 25: ...und if the mains power supply fails or is out of tolerance UPS shut down in case of battery operation 6 7 If in the case of battery operation a positive signal level 5 V to 12 VDC is applied for 500 ms the UPS system shuts down Battery capacity low 5 normally open PIN 5 is shorted with respect to PIN 4 if batteries have become discharged to such ...

Page 26: ...the remaining emergency supply period at full load is less than 2 minutes Normal mode 3 normally closed PIN 3 is shorted to PIN 4 during normal operation and opened if the mains power supply fails or is out of tolerance ...

Page 27: ...52 8 Appendix Figure 7 Front and back view of RITTAL PMC UPS 6KVA ...

Page 28: ...53 Figure 8 Front and back view of RITTAL PMC UPS 6KVA BatteryPack ...

Reviews: