SOLA 610

6 & 10kVA

50/60 Hz Single Phase

Uninterruptible Power System

Installation and

Operation Manual

Save these instructions!

This manual contains important instructions that should

be followed during installation and maintenance of the UPS.

Conserver ces instructions!

Cette notice contient des instructions importantes

concernant la securite!

Ref: 610MAN6K10K

Rev 2   Issued: September 97

Summary of Contents for 0610-010KA

Page 1: ...nstallation and Operation Manual Savetheseinstructions This manual contains important instructions that should be followed during installation and maintenance of the UPS Conservercesinstructions Cette notice contient des instructions importantes concernant la securite Ref 610MAN6K10K Rev 2 Issued September 97 ...

Page 2: ...This page intentionally left blank ...

Page 3: ...nnection 4 2 9 Inverter Shutdown Link Installation 5 2 10 Setting up the UPS monitoring from your computer 6 3 UPS Operation 3 1 Switching on the UPS 8 3 2 When the power fails 8 3 3 When the power returns 9 3 4 Front panel indicators 9 4 Optional Features 4 1 External Battery Options 10 4 2 Installing the CheckUPS II software 11 4 3 Operating CheckUPS II 13 4 4 Installation and Operation of the A...

Page 4: ...ction 5 6 of this manual Should you wish to upgrade the service guarantee to the premier FASTFIX exchange service or extend your warranty beyond the initial two years please contact your local SOLA office We encourage you to read this manual carefully in order to get full benefit from the features built into your SOLA product It is recommended that you register your purchase by completing the warr...

Page 5: ...erformance or use of this material This document contains proprietary information which is protected by copyright All rights are reserved No part of this document may be photographed reproduced or translated to another language without the prior written consent of SOLA This manual contains technical information about the following SOLA UPS systems iii Rating kVA Model No Part No Input Output Volta...

Page 6: ...the user s responsibility to remedy potential television and or radio interference The following FCC booklet may be helpful in resolving interference HowtoIdentifyandResolveRadio TVInterferenceProblems StockNumber004 00 00345 4 This booklet is available from the U S Government Printing Office Washington DC 20402 DEPARTMENT OF COMMUNICA T IONS NOTICE This digital apparatus does not exceed the Class...

Page 7: ...ARE NO USER SERVICEABLE PARTS INSIDE THE UPS 2 This unit is capable of supplying AC voltage even if there is no input present Although the System On Off Switch on the front of the UPS is protected from accidental actuation be careful the unit does not become unintentionally enabled 3 The SOLA 610 is not authorised for use as a critical component in life support devices without the express written ...

Page 8: ...OF ELECTRICAL SHOCK AND OR BURN FROM HIGH SHORT CIRCUIT CURRENT OBSERVE PROPER PRECAUTIONS UNE BATTERIE PEUT PRÉSENTER UN RISQUE DE CHOC ÉLECTRIQUE DE BRÛLURE PAR TRANSFER D ÉNERGIE SUIVRE LES PRÉCAUTIONS QUI S IMPOSENT 10 PROPER DISPOSAL OF BATTERIES IS REQUIRED REFER TO YOUR LOCAL CODES FOR DISPOSAL REQUIREMENTS L ÉLIMINATION DES BATTERIES EST RÈGLEMENTÉE CONSULTER LES CODE LOCAUX À CET EFFET 11...

Page 9: ...e UPS specifications as detailed for each model Your SOLA 610 is an advanced true on line sine wave UPS with bypass line utilising double conversion technology The utility power enters the UPS where it is rectified to a DC voltage which will float charge the battery as well as run the DC to AC inverter The inverter generates the true sine wave output recreating the utility supply voltage A bypass ...

Page 10: ...ging for your SOLA 610 was designed specifically for this unit and serves it well in protecting the unit from damage you should unpack the unit immediately and check for signs of concealed damage that may have occurred in transit Concealed damage is damage that may not be apparent by the outside appearance of the packaging In case of damage please notify the delivering carrier at once to examine t...

Page 11: ...rating 1500 m 0o C to 40o C 32o F to 104o F Temperature 1500 3000 m 10o C to 35o C Ambient Storage All Models 15o C to 40o C 5o F to 104o F Humidity All Models 20 to 95 non condensing Altitude All Models 8 000 feet 2500M max To optimise the performance of your UPS we recommend you ensure the battery is fully charged before you use the UPS to support your critical load To recharge the battery have ...

Page 12: ...heoutputreceptacles External battery options can be fitted to increase the autonomy when the UPS is operating during a mains failure Refer Section 4 1 for selection of external battery options for your specific UPS On the rear of the 6kVA UPS you will find an external battery receptacle For 10kVA models the external battery is hardwired to the terminal block If you have purchased an external batte...

Page 13: ...moved to avoid shipping damage Make sure the green remote inverter shutdown link has a loop of wire in the terminals and firmly insert it into the receptacle as shown IMPORTANTNOTICE If the inverter shutdown link is not installed with the wire loopfitted the UPS inverter W ILLNOT START Step 1 Step 2 Fitting the Inverter Shutdown Link The Inverter Shutdown Link Fitted 5 ...

Page 14: ...d with your UPS includes software for many standard operating systems and detailed manuals in Adobe Acrobat format All utilities required to read and or print the manuals are included on the CD ROM Refer to section 4 2 4 3 for more details of CheckUPS II and it s capabilities If you have purchased an AS400 card option this will be installed in the communications slot Be careful to connect your AS4...

Page 15: ...This page intentionally left blank 7 ...

Page 16: ...y now start the critical equipment that you connected to the UPS If the load level indicator exceeds 100 and the audible alarm sounds twice per second you have plugged too many items into the UPS and overloaded it Remove the non critical items and check the load level indicators When the utility AC source fails the UPS will continue to deliver output to the UPS receptacle from the internal or exte...

Page 17: ...different operating modes of the UPS When utility AC mains is present these will show the equipment load connect as a percentage of the UPS capacity in 25 increments When the UPS is in battery mode these lights will show the amount of battery capacity remaining as a percentage of the full battery capacity in 25 increments This light illuminates when the bypass line is in use and the UPS power is b...

Page 18: ...able on request When using this battery pack option batteries internal to the UPS are removed 10 Part Number To Suit U P S Model U P S R a tin g kVA Runtim e w ith U P S and additional battery pack Half Load F u ll Load 0 6 1 0 1 B A T 6 0 0 0 0 6 1 0 6 0 0 0 A 6 4 6 m in 2 3 m in 0 6 1 0 2 B A T 6 0 0 0 0 6 1 0 6 0 0 0 A 6 7 7 m in 3 6 m in 0 6 1 0 3 B A T 6 0 0 0 0 6 1 0 6 0 0 0 A 6 1 9 1 m in 7...

Page 19: ...obe Acrobat reader utility Installation The CheckUPS II Suite master installation program will auto detect which operating system you are running and ask you which UPS model you have connected to your system Then it will launch the appropriate software installation program Verify that the UPS is turned on and connected to the PC Exit any other currently running programs Insert the CheckUPS II Suit...

Page 20: ...d select Install manual only Once you have installed the software it will either start running automatically or you will be returned to the operating system This completes CheckUPS II software installation Installation Troubleshooting If for some reason the master installation program does not properly auto detect your operating system you may manually select an install program for your UPS by run...

Page 21: ...adings The Readingsgroup allows you to display seven values from the complete list of UPS values If you would like to change a reading or the properties of a reading just point to the reading and click The Reading Configuration window displays Pick a value from the ChooseDatatoDisplaylist box The values available will vary depending on the model of UPS Set the thresholds and assign colours to the ...

Page 22: ...ound colours will reflect the thresholds If you also display the value as a reading the same thresholds are used When you finish configuring the meter click OK If you wish to clear the thresholds click Clear If you would like to reset the thresholds to their suggested values click Defaults If you would like to abandon all changes and close the Meter Configuration window click Cancel ExitingCheckUP...

Page 23: ...utton to display the Configure User Defined Events window User DefinedEventConfiguration User defined events are based on UPS values You can configure a value or range of values to define an event then use the event to trigger actions Select a UPS value on which your event will be based Next select the criteria that defines when the event occurs You can use the andor the or check box to combine co...

Page 24: ...hutdownEnabled and configure a Delay The delay starts when the event is detected Next you may wish to turn UPS output power off If so select UPSShutdown Enabledand configure a Delay The delay starts when the event is detected Warning Shutting down the UPS without first shutting down the operating system could result in loss of data A lways add enough time for the operating systemto shut down befor...

Page 25: ... to the suggested values click Defaults If you want to abandon changes click Cancel Broadcasting If you haven t already selected Configure Action from the main menu bar please select it now In the Event Action Configuration window click the Broadcastingcommand button to display the Broadcasting Configuration window If you select the BroadcastingEnabledcheck box a check mark will appear on the Broa...

Page 26: ...nt to the modem The InitializationStringallows you to configure the modem to return result codes The result codes allow CheckUPS II Advanced to determine the status of the page The default string is ATE0Q0V0X4 The meanings of the codes follow AT Attention code E0 Turns echo off so commands are not echoed back to the computer Q0 Enables result code return to the computer V0 Enables numeric result c...

Page 27: ...iguring CheckUPS II Advanced for the third of five systems located in room 122 of the building To acquire an outside telephone line from your phone system you must dial 9and wait for the dial tone For example the telephone number for the paging service is 18005551212 The Dial Prefix would be ATDT9W If it took the paging service approximately ten seconds to answer and get ready to accept the paging...

Page 28: ...lues to choose from The available UPS values depend on the UPS model Click ConfigureAddresses to display the Current List of Email Addresses window The modem configuration can also be displayed by choosing the Configure Email menu option To configure Email addresses click the Addcommand button To modify an existing Email address click on the address and click Modify To delete an address from the C...

Page 29: ...ack power events and trends Data can be viewed in text and graphical form Events can be viewed events in text form You can print both data and event files LoggingConfiguration Before CheckUPS II Advanced begins data logging you must configure what data is logged For convenience you can also configure the event log from the same window To display the Logging Configuration window select the Configur...

Page 30: ...king the Options command button If you click the Options command button the Graph Options window displays Select Scatter Line or Barfor the GraphType Select the RangeonScreenand HoursorDaysto define the X axis range and units Depending on GraphType choose to display the Average Minimums Maximums or all three Averagevalues are graphed in blue Minimumsare graphed in green Maximumsare graphed in red ...

Page 31: ... file click Exitto close the window EventLogViewer After events accumulate you can view the event log To display the log select the View EventLog menu option Use the vertical and horizontal scroll bars to view all of the rows and columns in the table To limit the types of events displayed in the table select one or more of the check boxes in the ViewEventTypes group box The event type category nam...

Page 32: ...Addcommand button The Scheduling Configuration window displays Select an action from the Actiongroup box Select the Timeand the frequency of the action The available actions depend on the UPS model The GracePeriodis the time interval between when the operating system shutdown is started and when the UPS output power is shut off Make sure the GracePeriodyou select allows your system to shut down pr...

Page 33: ...ications slot on the rear of the UPS The AS400 card option is fitted with two 2 connectors one DB9 female and one ES 2 pin The output available from these connectors is as follows Output 1 DB9 female connector 4 4 InstallationandOperationofthe AS400 cardoption P in No S ignal Name D e finition I O C o m m e n ts 1 U P S F a i l Normally open Active will close O R e lay contact 2 S ummary Alarm Nor...

Page 34: ...ons slot cover plate for reinstallation should the AS400 card option be removed and decommissioned in the future 4 The AS400 card will now be operational when the UPS is turned on and returned to service Output 2 ES 2 Pin connector 4 4 InstallationandOperationofthe AS400 card option 26 A plug with link is supplied with the AS400 card option This plug must be installed for normal operation If this ...

Page 35: ...MP adaptor card One female male connector cable for connecting the SNMP adaptor card to a PC or terminal for configuration One 3 5 DOS formatted diskette containing the UPS SNMP Agent MIB One 3 5 tar formatted diskette containing the UPS SNMP Agent MIB One User s Configuration and Operations Manual To install the SNMP adaptor card complete the following 1 Shutdown the UPS remove your connected loa...

Page 36: ...uld be inspected for signs of damage and repaired if necessary If you would like to clean the unit first remove all power to the unit by turning OFF the unit at the System On Off switch and isolate the unit from the input supply by disconnecting the supply at the distribution board If the unit is operating in an unusually dusty or dirty area carefully vacuum any dust from the input vents as well a...

Page 37: ...C ircuit B reaker Output C ircuit B reaker Troubleshooting Chart Problem Possible Cause Action to Take No Lights No Alarms UPS not ON Rear panel fuse blown or circuit protector tripped Replace fuse or reset protector Restart UPS No incoming utility Check input power No AC Line light alarm beeps every few seconds No incoming utility Check input power Fuse blown or protector tripped Replace fuse or ...

Page 38: ...seconds Connection Hardwired Efficiency AC to AC Efficiency 80 minimum full load 0 7 pf fully charged batteries Battery Type Sealed Maintenance Free 12V Cell Battery System Voltage 240V DC Runtime 0 8pf 6kVA Full Load 9 min Half Load 25 min 10kVA Full Load 12 min Half Load 30 min Bypass UPS to from Bypass Transfer Time 0 msec Auto reverse Returns to normal mode after overload condition removed Aco...

Page 39: ...th m m Height m m Weight kg 0610 6000A 260 550 710 115 0610 010KA 340 656 980 200 B a t t e r y P a c k s Model W idth m m Depth m m Height m m Weight kg 0610 1BAT 6000 260 555 710 80 0610 2BAT 6000 260 710 555 160 0610 1BAT 010K 380 774 1045 222 0610 2BAT 010K 380 774 1045 272 Specification subject to change without notice ...

Page 40: ...ct to Sola Australia are at the customer s expense For hardwired products 3kVA and above the Warranty covers on site repair Metropolitan area Capital Cities only during normal working hours by Sola technicians or appointed agents For units installed in remote locations Sola Australia may at its discretion request the equipment to be recovered and returned to the factory or other nominated service ...

Page 41: ...n a non original container will void this warranty For proper handling upon receipt at SOLA the R A Number must be clearly placed in several locations on the outside of the package SOLA will not be responsible for damage to returned goods that have not been properly packaged or damage exceeding normal wear and tear ForServiceinAustralia contact 1800034401 CallersoutsideMelbourne or 97683105 Melbou...

Page 42: ... You have purchased a UPS that will provide you with many years of service protecting your equipment from surges sags and blackouts This product incorporates the highest quality standards in engineering manufacturing and testing and carries a 2 year warranty against defects in material and workmanship This product is backed by over 60 years of pride and integrity We are sure you will agree there i...