background image

 

 

 

 

 
 
 
 

Rack/Tower Online UPS 

1K/1.5K/2K/3K 

 
 
 
 
 
 
 
 
 

Uninterruptible Power Supply System 

Version: 1.2 

 

User Manual 

Summary of Contents for Online UPS 1K

Page 1: ...Rack Tower Online UPS 1K 1 5K 2K 3K Uninterruptible Power Supply System Version 1 2 User Manual...

Page 2: ...view 3 2 2 Install the UPS 4 2 3 Setup the UPS 5 2 4 Battery Replacement 6 2 5 Battery Kit Assembly option 7 3 Operations 10 3 1 Button operation 10 3 2 LCD Panel 10 3 3 Audible Alarm 12 3 4 LCD disp...

Page 3: ...over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...al package in a safe place for future use NOTE There are two different types of online UPS standard and long run models Please refer to the following model table Model No Type Model No Type 1K Standar...

Page 6: ...ong run models 11 Input terminal 12 Output circuit breaker 2 2 Install the UPS For safety consideration the UPS is shipped out from factory without connecting battery wires Before install the UPS plea...

Page 7: ...port Intelligent slot To allow for unattended UPS shutdown start up and status monitoring connect the communication cable one end to the USB RS 232 port and the other to the communication port of your...

Page 8: ...m 2 Click ViewPower software icon and then choose your required OS to download the software 3 Follow the on screen instructions to install the software 4 When your computer restarts the monitoring sof...

Page 9: ...the unit 2 5 Battery Kit Assembly option NOTICE Please assemble battery kit first before installing it inside of UPS Please select correct battery kit procedure below to assemble it 2 battery kit Ste...

Page 10: ...battery packs on one side of plastic shells and insert one more defect battery on the space Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 4 battery kit...

Page 11: ...ow chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on one side of pl...

Page 12: ...e if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the...

Page 13: ...voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuited UPS status Indicates that progr...

Page 14: ...D display wordings index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape RAC Rack display TOE Tower display B L Low Battery O L Overload N C Battery is not connected O C Overcha...

Page 15: ...127 VAC models you may choose the following output voltage 100 presents output voltage is 100Vac 110 presents output voltage is 110Vac 115 presents output voltage is 115Vac 120 presents output voltage...

Page 16: ...isable Interface Setting ENA Advanced ECO mode enable DIS Advanced ECO mode disable 06 Bypass mode enable disable Interface Setting ENA Bypass mode enable DIS Bypass mode disable 07 Programmable outle...

Page 17: ...the following Acceptable input voltage range 110 300 alternating flashing acceptable input voltage range is from 110V to 300V 160 260 alternating flashing acceptable input voltage range is 160V to 26...

Page 18: ...y Corrective Optimizer When the input voltage is within setting range 3 Vo max UPS will bypass voltage to output for energy saving PFC and INVERTER are off at this mode Frequency Converter mode When i...

Page 19: ...nder 03 x Battery voltage too high 27 x Bus unbalance 04 x Battery voltage too low 28 Inverter soft start fail 11 x Over temperature 41 x High Inverter voltage 12 x Overload 43 3 8 Warning indicator W...

Page 20: ...hing on LCD display and alarm is sounding every second The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon is lig...

Page 21: ...ring and if connected devices are in short circuit status Fault code is shown as 01 02 03 04 11 12 13 and 41 on LCD display and alarm is continuously sounding A UPS internal fault has occurred There a...

Page 22: ...ealer Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperat...

Page 23: ...12V 9Ah Depending on application 12V 9Ah Depending on application 12V 9Ah Depending on application Numbers 2 3 4 6 Typical Recharge Time 4 hours recover to 90 capacity for standard model only Charging...

Reviews: