Connecting the CL-NET
network
69
1SVC 440 795 M1100
Table 5:
Pre-assembled cables, RJ45 plug on both ends
Material for unassembled cables
e.g.: 4 × 0.18 mm
2
Bus termination resistor
The first and last stations in the network must be provided
with a bus termination resistor.
• Value: 124
O
• Termination plug: CL-LAD.TK009
Cable length with cross-sections
For correct operation of the network the cable lengths,
cross-sections and cable resistances must match those listed
in the following table.
The impedance of the cables used must be 120
O
.
Cable length
Type designation
cm
30
CL-LAD.TK002
80
CL-LAD.TK003
150
CL-LAD.TK004
Cable length
Cable resistance
Cross-section
m
m
O
/m
mm
2
AWG
Up to 40
F
140
0.13
26
Up to 175
F
70
0.25 to 0.34
23, 22
Up to 250
F
60
0.34 to 0.5
22, 21, 20
Up to 400
F
40
0.5 to 0.6
20, 19
Up to 600
F
26
0.75 to 0.8
18
Up to 1000
F
16
1.5
16
h
The installation of an expensive fibre optic link is
recommended with cable lengths > 500 m.