Appendix
402
1SVC 440 795 M1100
Relay outputs
CL-LDR…
Number
4
Type of outputs
Relays
In groups of
1
Parallel switching of outputs to increase performance
Not permissible
Protection of an output relay
Miniature circuit-breaker B16
A
16
or fuse (slow-blow)
A
8
Potential isolation to the power supply, inputs, PC interface, memory
module, CL-NET, CL-LINK network
Yes
Safe isolation
V AC
300
Basic insulation
V AC
600
Mechanical lifespan
Switch
operations
10 × 10
6
Contacts relays
Conventional thermal current, (UL)
A
8, (10)
Recommended for load at 12 V AC/DC
mA
> 500
Protected against short-circuit cos
v
= 1
16 A characteristic B (B16) at
A
600
Protected against short-circuit cos
v
= 0.5 to 0.7
16 A characteristic B (B16) at
A
900
Rated impulse withstand voltage
U
imp
contact coil
kV
6
Rated insulation voltage
U
i
Rated operational voltage
U
e
V AC
250
Safe isolation to EN 50178 between coil and contact
V AC
300
Safe isolation to EN 50178 between two contacts
V AC
300