Wiring with the display system
264
1SVC 440 795 M1100
Entering function block parameters from the circuit
diagram.
You can access the parameter entry from the contact as well
as from a coil.
X
Enter the circuit diagram up to
C 01
as a coil.
C 01C
is the counter coil of the counter 01 function block.
Figure: 145:
Display system wiring and circuit diagram
X
Keep the cursor on the number.
X
Press the
OK
button.
The first part of the parameter set of a counter is displayed.
X
Move the cursor
í
over the
+
character to the value input
behind
>SH
:
–
> SH
means: Function block input upper counter
setpoint value
– The
+
character means that the parameters of this timing
relay can be modified using the PARAMETERS menu.
X
Change the upper counter setpoint to 10:
– Use
ú í
to move the cursor onto the tens digit.
– Use
ÍÚ
to modify the value of the digit.
X
Press
OK
to save the value and
ESC
to return to the circuit
diagram.
X
Enter the circuit diagram up to contact
T 01
of the timing
relay. Set the parameter for
T 01
.
I 05---------------------------Ä C 01C
I 06---------------------------Ä C 01RE
C 01---------------------------Ä T 01EN
T 01Q1-------------------------Ä Q 01
h
If the cursor is on the contact number, the display system
will call up the parameter display when you press
OK
.
C 01
+
>SH +10
>SL
>SV
h
The display system has specific parameter displays for the
function blocks. The meaning of these parameters is
explained under each function block type.
Содержание CL Series
Страница 1: ... APPLICATION MANUAL Display system CL range ...
Страница 115: ...112 1SVC 440 795 M1100 ...
Страница 345: ...342 1SVC 440 795 M1100 ...
Страница 427: ...1SVC 440 795 M1100 424 ...