![ABB CL Series Скачать руководство пользователя страница 156](http://html.mh-extra.com/html/abb/cl-series/cl-series_applications-manual_4582156.webp)
Function blocks
153
1SVC 440 795 M1100
Parameter display and parameter set for analog value
comparators:
Inputs
The function block inputs
>I1
,
>F1
,
>I2
,
>F2
,
>OS
and
>HY
can have the following operands:
• Constants
• Markers MD, MW, MB
• Analog inputs IA01 to IA04
– IA01: Terminal I7
– IA02: Terminal I8
– IA03: Terminal I11
– IA04: Terminal I12
• Analog output QA01
• Actual value …QV> of another function block
Analog value comparator operating modes
Contacts
A 01Q1 to A 32Q1
A 02 GT
+
>I1
>F1
>I2
>F2
>OS
>HY
A 02
Analog value comparator function block number 02
GT
Greater than mode
+
Appears in the parameter display
>I1
Comparison value 1
>F1
Gain factor for
>I1
(
>I1
=
>F1
x
value)
>I2
Comparison value 2
>F2
Gain factor for
>I2
(
>I2
=
>F2
x
value)
>OS
Offset for the value of
>I1
>HY
Switching hysteresis for value
>I2
(Value
HY
applies to
positive and negative hysteresis.)
Parameter
Function
GT
>I1
greater than
>I2
EQ
>I1
equal to
>I2
LT
>I1
less than
>I2