Function blocks
207
1SVC 440 795 M1100
Actual value …QV>
The actual value …QV> can be assigned the following
operands:
• Markers MD, MW, MB
• Analog output QA01
Value range for inputs and outputs
Example:
Displaying the parameter set in the PARAMETERS
menu
• + Access enabled
• – Access disabled
Value range
Resolution/unit
>I1
Setpoint of PID controller
–32768 to +32767
>I2
Actual value of PID controller
–32768 to +32767
>KP
Proportional gain K
p
0 to 65535
in -- /%
>TN
Reset time T
n
0 to 65535
in 100/ms
>TV
Rate time T
v
0 to 65535
in 100/ms
>TC
Scan time
0 to 65535
in 100/ms
>MV
Manual manipulated variable
–4096 to +4095
QV>
Manipulated variable
0 to 4095 (unipolar)
–4096 to +4095 (bipolar)
Value at input
Value processed in
the function block.
>KP
Proportional gain K
p
1500
15
>TN
Reset time T
n
250
25 s
>TV
Rate time T
v
200
20 s
>TC
Scan time
500
50 s
>MV
Manual manipulated variable
500
500