Configuration of the
CL-NET network
331
1SVC 440 795 M1100
Signs of life of the individual stations and diagnostics
The inputs and outputs message type is used as a “sign of
life” recognition to ensure that the state of a station can be
recognised by other stations. The states of the inputs and
outputs are sent cyclically and at the set baud rate,
irrespective of the SEND IO setting. If the inputs and outputs
of a station are not recognised by other stations after a time
determined by the baud rate, the station is deemed to be
disconnected until the next “sign of life” is recognised.
Evaluation occurs at the following intervals:
Baud rate
Stations must send a
“sign of life” every …
Station detects a missing
sign of life signal from
[KB]
[ms]
[ms]
1000
60
180
500
60
180
250
120
360
125
240
720
50
600
1800
20
1500
4500
10
3000
9000