Set Up Control Page
…4
CONFIGURATION
Heat Output High Limit
This limits the high level of the Heat control output value when
in Automatic mode. If the control output is above this limit
when Automatic mode is selected, the output is allowed to
stay at its current level but is not allowed to go any higher.
Once the control output returns to, or below, this limit the limit
then applies. When the controller is in Manual mode the
output limits do not apply. Select the heat output high limit
value required, between 0.0 and 100.0% in 0.1 increments.
Cool Output High/Low Limit
This limits the high or low level of the Cool control output
when in Automatic mode, depending on the
Control Action
(Cool)
frame setting (
rEV
is the low and
dIr
is the high
setting). If the control output exceeds this limit when
Automatic mode is selected, the output remains at its current
level but is not allowed to go any further away from the limit.
Once the control output returns to, or within, this limit, the limit
then applies. When the controller is in Manual mode the
output limits do not apply. Select the Cool output high (low)
limit required, between 0.0 and 100.0% in 0.1 increments.
Continued on the next page.
Ht–HI
I00.0
CL–HI
100.0
SINGLE
P-PrOP
bNdLSS