Page Header – Set Up Remote Set Point Input.
Remote Set Point Input Type
Select the input type required:
MVLt
–
Millivot (
≤
2000mV)
MAMP
–
Current
VOLt
–
Voltage
ohM
–
Resistance
tCPL
–
Thermocouple*
rtd
–
Resistance thermometer
*For thermocouple applications using an external fixed
cold junction, select millivolt input type.
Remote Set Point Linearizer Type
Select the linearizer type required:
NONE
–
No linearizer
tC-K
–
Type K thermocouple
tC-r
–
Type R thermocouple
tC-S
–
Type S thermocouple
tC-t
–
Type T thermocouple
tC-J
–
Type J thermocouple
tC-L
–
Type L thermocouple
tC-E
–
Type E thermocouple
tC-b
–
Type B thermocouple
tC-N
–
Type N thermocouple
rtd
–
Resistance thermometer
SQrt
–
Square root
3/2
–
x
3/2
5/2
–
x
5/2
Linearizer Units
Select the temperature units required,
°
C or
°
F.
Linearizer Full Scale
Set the range maximum temperature in
°
C or
°
F as
selected at
Linearizer Units
above, within the limits detailed
in Table 4.1. If limits are exceeded,
LIN–Or
(linearizer
overrange) is displayed in the
Operating Page
– see
Table
5.1a of the Operating Guide.
Continue on next page.
4.6
Set Up Remote Set Point Page
Information.
•
This page is omitted if Remote set point is not selected at Second Set Point Type in Set
Points Page – see Section 4.2.
•