22
SEtUP
PSN–Fb
IntYP3
VOLt
MAMP
MVLt
135.0
dEC–Pt
r–HI–3
r–LO–3
ohM
0.0
135.0
bSPd– 3
UP
dN
NONE
FdLP–3
10.0
…4
CONFIGURATION
4.7
Set Up Position Feedback Page
Information.
•
This page is only present if
P–PrOP
or
bndLSS
is selected at Control Type in the Set
Up Control Page – see Fig. 3.1 and Section 4.10. If
bndLSS
is selected, Position
Feedback Enable must be set to
INdCtN
to enable access to this page.
•
Millivolt, current, voltage or resistance input.
•
Programmable fault level and actions.
Page Header – Set Up Position Feedback.
Position Feedback Input Type
Select the input type required:
MVLt
–
Millivolt
≤
2000mV
MAMP
–
Current
VOLt
–
Voltage
ohM
–
Resistance
Position Feedback Range Full Scale
Set the position feedback range full scale value, within the
limits of
Table 4.2
– see page 18.
Decimal Point Position
Set the decimal point position required for both the position
feedback range full scale and range zero values.
Position Feedback Range Zero
Set the position feedback range zero value, within the
limits of
Table 4.2
– see page 18.
Broken Sensor Protection Drive
In the event of a fault being detected on the input, the
remote set point is driven in the direction of the mode
selected.
Select the broken sensor drive required:
NONE
for no
drive,
UP
for upscale drive or
dN
for downscale drive.
Fault Detection Level Percentage, Position Feedback
Input
A fault level percentage can be set to detect a deviation
above or below the display limits, e.g. If set to 10.0%, then
if the position feedback input deviates by more than 10%
above Full Scale value or 10% below zero value, a fault is
detected. Position feedback action in the event of a fault is
programmable, see
Default Action
.
Set the value required, between 0.0 and 100.0%.
Continued on next page.