50
…4
CONFIGURATION
…4.16
Set Up Process Variable Input Page (COMMANDER 301 only)
Electrical Decimal Point
Enter the number of decimal point positions required for
the electrical input range (0 to 2).
Engineering Decimal Point
Enter the number of decimal point positions required for
the engineering temperature range (0 to 3).
Break Point Selection
Select the break point to be set up and press
to move
to
Electrical Break Point.
Note. The engineering range (display range) is set
automatically and cannot be adjusted.
Electrical Break Point
Enter the value in electrical units (Millivolts, Milliamps,
Ohms or Volts), for the break point selected above. It is not
necessary to enter all 20 break points. The instrument
ignores any break point that has an electrical value lower
than the previous one and all the break points which follow
it.
Engineering Break Point
Enter the value in engineering units for the break point
selected above.
Press
to return to the break point selection frame. Note
that the break point selected will automatically be
increased to the next one when this is done.
Continued on the next page.
1
1
ENG–dP
ELECdP
ELECbP
0.0
ENG–bP
0.0
xx
brKPNt
750
°
C
1 2
3 4
5
6
7
8
9
Electrical
Range
Engineering Range
300
°
C
Electrical Break Points
Engineering
Break Points
4.0 mA
20.0 mA