Profile Program Page
4
CONFIGURATION…
Program End (finish level)
Set the program end level number for the program chosen
at
Program Select
, between 1 and 30 (12 for C301, 99 for
C302).
Program First Segment Start Level
The number shown in the upper display is the start level
number for the first segment.
Set the required value for the start level.
The units are display units between
Display Zero
and
Display Full Scale.
Segment Time Period
The time number of the currently selected segment is
shown in the upper display.
Set the required time period, between 0 and 999.9 minutes
in 0.1 minute increments.
Segment Finish/Start Level
The number shown in the upper display is the finish level
number for the currently selected segment and the start
number for the next segment.
Set the required value for the segment finish/start level. The
units are display units between display zero and full scale.
Advance to the next parameter,
Segment Time Period
, if
more segments are to be set-up or
Repeat
if the current
segment is the last segment.
Program Repeat
Each program can be set to repeat up to 99 times or
continuously.
Set the required repeat count, between 0 and 99, or
InFntE
for continuous repeats.
Program Hysteresis Value (for guaranteed ramp/soak)
A hysteresis value can be set in engineering units. Setting
the value to zero turns the guaranteed ramp/soak facility
off. If the process variable deviates beyond the value set,
the program is suspended but continues automatically
when the process variable returns within the set limits. The
hysteresis value applies above and below set point under
all program conditions.
Set the hysteresis value required, within the display range
limits.