![ABB C310 Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/abb/c310/c310_programming-manual_3052157019.webp)
16
…4
CONFIGURATION
4.5.1
Set Up Process Variable Input Page (COMMANDER 300)
If the custom linearizer is to be used (available on COMMANDER 301 only), refer to Section
4.16.
LNtYPI
NONE
tC-K
tC-r
tC-S
tC-J
tC-L
tC-E
rtd
SQrt
tC-t
3 2
5 2
SQrt
NONE
L–UNtI
dEG C
5 2
3 2
tC-b
tC-N
SEtUP
PrCESS
IntYPI
U.Lt
MAMP
VOLt
ohM
tCPL
rtd
(a)
(b)
Page Header –
Set Up Process Variable Input
.
Process Variable Input Type
Select the input type required:
MU.Lt
–
Millivolt (
≤
2000 mV)
MAMP
–
Current
V.OLt
–
Voltage
ohM
–
Resistance
tCPL
–
Thermocouple *
rtd
–
Resistance thermometer
*For thermocouple applications using an external fixed
cold junction, select millivolt input type.
Linearizer Type
Select the linearizer type required:
NONE
–
No linearizer
tC-K
–
Type K thermocouple
tC-r
–
Type R thermocouple
tC-S
–
Type S thermocouple
tC-t
–
Type T thermocouple
tC-J
–
Type J thermocouple
tC-L
–
Type L thermocouple
tC-E
–
Type E thermocouple
tC-b
–
Type B thermocouple
tC-N
–
Type N thermocouple
rtd
–
Resistance thermometer
SQrt
–
Square root
3 2
–
x
3/2
5 2
–
x
5/2
Linearizer Units
Select the temperature units required,
°
C or
°
F.