Set Up Control Page
4
CONFIGURATION…
Power Fail
Mode
Mode on
Power Down
Mode on
Power Up
Control Output (Valve Position
on Power Up
Auto
Auto
Auto
Integral component of the control output is preset to
give bumpless operation at power-up at the value set
in the Auto-to-Auto frame.
Manual
Auto
Integral component of the control output is preset to
give bumpless operation at power-up at the value set
in the Manual-to-Auto frame (or LAST)
Manual
Auto
Manual
Value set in Auto-to-Manual Output frame (or LAST)
Manual
Manual
Value set in Manual-to-Manual Output frame or
output value prior to power-down (if LAST selected)
Last
Auto
Auto
Integral component of the control output is preset to
give bumpless operation at power-up at the value set
in the Auto-to-Auto frame (or LAST)
Manual
Manual
Value set in Manual-to-Manual Output frame or
output value prior to power-down (if LAST selected)
Table 4.3 Power-up and Power-down Control Modes
Power Fail Indication Enable
If the indication is enabled,
LINE FAILEd
is displayed in
the
Operating Page
following a power failure.
Select
YES
to enable or
no
to disable indication.
Failure Message
The following
Operating Page
Failure messages can be
enabled or disabled – see
Section 5.2 of Operating Guide.
F–INPt
– process input failure
F–rSPt
– remote set point failure
F–POSN
– position feedback failure
Select
YES
to enable or
no
to disable.
Auto/Manual Switch Enable/Disable
Select
on
to enable, or
OFF
to disable.
If
HEAtCL
is selected at
Control Mode
, advance to
Control
Action (Heat)
, otherwise advance to
Output High Limit.
Continued on next page.