Parameters 185
24.06
Torq ramp up
Defines the torque reference ramp-up time, i.e. the time for
the reference to increase from zero to the nominal motor
torque.
0.000 … 60.000 s
Torque reference ramp-up time.
1000 = 1 s
24.07
Torq ramp down
Defines the torque reference ramp-down time, i.e. the time for
the reference to decrease from the nominal motor torque to
zero.
0.000 … 60.000 s
Torque reference ramp-down time.
1000 = 1 s
25
25 Critical speed
Sets up critical speeds, or ranges of speeds, that are avoided
due to, for example, mechanical resonance problems.
25.01
Crit speed sel
Enables/disables the critical speeds function.
Example:
A fan has vibrations in the range of 540 to 690 rpm
and 1380 to 1560 rpm. To make the drive to jump over the
vibration speed ranges:
• activate the critical speeds function,
• set the critical speed ranges as in the figure below.
Disable
Critical speeds are disabled.
0
Enable
Critical speeds are enabled.
1
25.02
Crit speed1 lo
Defines the low limit for critical speed range 1.
Note:
This value must be less than or equal to the value of
.
-30000 … 30000
rpm
Low limit for critical speed 1.
1 = 1 rpm
25.03
Crit speed1 hi
Defines the high limit for critical speed range 1.
Note:
This value must be greater than or equal to the value of
.
-30000 … 30000
rpm
High limit for critical speed 1.
1 = 1 rpm
No.
Name/Value
Description
FbEq
540
690
1380
1560
1
= 540 rpm
2
= 690 rpm
3
= 1380 rpm
4
= 1590 rpm
1
2
3
4
Motor speed
(rpm)
Drive speed
(rpm)
Drive speed
(rpm)
Содержание ACS850 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Страница 4: ......
Страница 56: ...56 Control locations and operating modes ...
Страница 262: ...262 Parameters ...
Страница 310: ...310 Fault tracing ...
Страница 348: ...348 Control through a fieldbus adapter ...
Страница 358: ...358 Drive to drive link ...
Страница 368: ...368 Control chain and drive logic diagrams ...