Parameters 219
40.03
Slip gain
Defines the slip gain which is used to improve the estimated
motor slip. 100% means full slip gain; 0% means no slip gain.
The default value is 100%. Other values can be used if a
static speed error is detected despite of the full slip gain.
Example
(with nominal load and nominal slip of 40 rpm): A
1000 rpm constant speed reference is given to the drive.
Despite of the full slip gain (= 100%), a manual tachometer
measurement from the motor axis gives a speed value of 998
rpm. The static speed error is 1000 rpm - 998 rpm = 2 rpm. To
compensate the error, the slip gain should be increased. At
the 105% gain value, no static speed error exists (2 rpm / 40
rpm = 5%).
0 … 200%
Slip gain.
1 = 1%
40.04
Voltage reserve
Defines the minimum allowed voltage reserve. When the
voltage reserve has decreased to the set value, the drive
enters the field weakening area.
If the intermediate circuit DC voltage
U
dc
= 550 V and the
voltage reserve is 5%, the RMS value of the maximum output
voltage in steady-state operation is
0.95 × 550 V / sqrt(2) = 369 V
The dynamic performance of the motor control in the field
weakening area can be improved by increasing the voltage
reserve value, but the drive enters the field weakening area
earlier.
-4 … 50%
Voltage reserve.
1 = 1%
40.06
Force open loop
Defines the speed/position information used by the motor
model.
False
Motor model uses the speed feedback selected by parameter
.
0
True
Motor model uses the internal speed estimate (even when
parameter
is set to
).
1
No.
Name/Value
Description
FbEq
Содержание ACS850 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Страница 4: ......
Страница 56: ...56 Control locations and operating modes ...
Страница 262: ...262 Parameters ...
Страница 310: ...310 Fault tracing ...
Страница 348: ...348 Control through a fieldbus adapter ...
Страница 358: ...358 Drive to drive link ...
Страница 368: ...368 Control chain and drive logic diagrams ...