Control through the embedded fieldbus interface 323
7
RESET
0=>1
Fault reset if an active fault exists. Proceed to
SWITCH-
ON INHIBITED
.
Note:
This bit is effective only if the fieldbus interface is
set as the source for this signal by drive parameters.
0
Continue normal operation.
8, 9 Reserved.
10 REMOTE_
CMD
1
Fieldbus control enabled.
0
Control Word <> 0 or Reference <> 0: Retain last Control
Word and Reference.
Control Word = 0 and Reference = 0: Fieldbus control
enabled. Reference and deceleration/acceleration ramp
are locked.
11
EXT_CTRL_
LOC
1
Select External Control Location EXT2. Effective if the
control location is parameterized to be selected from the
fieldbus.
0
Select External Control Location EXT1. Effective if the
control location is parameterized to be selected from the
fieldbus.
12
…15
Reserved
Bit
Name
Value
STATE/Description