22 The ACS850 control panel
Basic operations – Any mode
How to start, stop and switch between local and remote control
You can start, stop and switch between local and remote control in any mode. To be
able to start or stop the drive by using the control panel, the drive must be in local
control.
Step
Action
Display
1.
To switch between remote control (REM shown on the
status line) and local control (LOC shown on the status
line), press
.
Note:
Switching to local control can be prevented with
.
The very first time the drive is powered up, it is in remote
control (REM) and controlled through the drive I/O
terminals. To switch to local control (LOC) and control the
drive using the control panel, press
. The result
depends on how long you press the key:
If you release the key immediately (the display flashes
“Switching to the local control mode”), the drive stops.
Set the local control reference as instructed on page
.
If you press the key until the text “Keep running” appears,
the drive continues running as before. The drive copies
the current remote values for the run/stop status and the
reference, and uses them as the initial local control
settings.
To stop the drive in local control, press
.
The arrow ( or ) on the status line
stops rotating.
To start the drive in local control, press
.
The arrow ( or ) on the status line
starts rotating. It is dotted until the
drive reaches the setpoint.
LOC
REM
00:00
Switching to the
local control mode.
MESSAGE
LOC
LOC
REM
Содержание ACS850 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Страница 4: ......
Страница 56: ...56 Control locations and operating modes ...
Страница 262: ...262 Parameters ...
Страница 310: ...310 Fault tracing ...
Страница 348: ...348 Control through a fieldbus adapter ...
Страница 358: ...358 Drive to drive link ...
Страница 368: ...368 Control chain and drive logic diagrams ...