Parameters 173
21.10
Mot pot func
Selects whether the value of the motor potentiometer is
retained upon drive power-off.
Reset
Drive power-off resets the value of the motor potentiometer.
0
Store
The value of the motor potentiometer is retained over drive
power-off.
1
21.11
Mot pot up
Selects the source of motor potentiometer up signal.
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
DI6
Digital input DI6 (as indicated by
, bit 5).
1074070017
Const
Bit pointer setting (see
on page
).
-
Pointer
21.12
Mot pot down
Selects the source of motor potentiometer down signal.
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
DI6
Digital input DI6 (as indicated by
, bit 5).
1074070017
Const
Bit pointer setting (see
on page
).
-
Pointer
22
22 Speed ref ramp
Speed reference ramp settings.
22.01
Acc/Dec sel
Selects the source that switches between the two sets of
acceleration/deceleration times defined by parameters
0 = Acceleration time 1 and deceleration time 1 are in force
1 = Acceleration time 2 and deceleration time 2 are in force.
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
DI6
Digital input DI6 (as indicated by
, bit 5).
1074070017
Const
Bit pointer setting (see
on page
).
-
Pointer
22.02
Acc time1
Defines acceleration time 1 as the time required for the speed
to change from zero to the speed value defined by parameter
If the speed reference increases faster than the set
acceleration rate, the motor speed will follow the acceleration
rate.
If the speed reference increases slower than the set
acceleration rate, the motor speed will follow the reference
signal.
If the acceleration time is set too short, the drive will
automatically prolong the acceleration in order not to exceed
the drive torque limits.
0.000 … 1800.000
s
Acceleration time 1.
1000 = 1 s
No.
Name/Value
Description
FbEq
Содержание ACS850 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Страница 4: ......
Страница 56: ...56 Control locations and operating modes ...
Страница 262: ...262 Parameters ...
Страница 310: ...310 Fault tracing ...
Страница 348: ...348 Control through a fieldbus adapter ...
Страница 358: ...358 Drive to drive link ...
Страница 368: ...368 Control chain and drive logic diagrams ...