308 Fault tracing
0209
STACK ERROR
(0x6100)
Drive internal fault
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0210
JMU MISSING
(0xFF61)
JMU Memory Unit is missing or
broken.
Check that the JMU is properly installed.
If the problem persists, replace the JMU.
0301
UFF FILE READ
(0x6300)
File read error
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0302
APPL DIR CREATION
(0x6100)
Drive internal fault
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0303
FPGA CONFIG DIR
(0x6100)
Drive internal fault
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0304
PU RATING ID
(0x5483)
Drive internal fault
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0305
RATING DATABASE
(0x6100)
Drive internal fault
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0306
LICENSING
(0x6100)
Drive internal fault
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0307
DEFAULT FILE
(0x6100)
Drive internal fault
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0308
APPLFILE PAR
(0x6300)
Corrupted application file
Note:
This fault cannot be
reset.
Reload application.
If fault is still active, contact your local
ABB representative.
0309
APPL LOADING
(0x6300)
Application file incompatible or
corrupted
Note:
This fault cannot be
reset.
Check the fault logger for a fault code
extension. See appropriate actions for
each extension below.
*Refer to
Application programming for
ACS850 drives
(3AUA0000078664
[English]).
Extension: 8
Template used in the
application incompatible with
drive firmware.
*Change the template of the application
in DriveSPC.
Extension: 10
Parameters defined in the
application conflict with
existing drive parameters.
*Check the application for conflicting
parameters.
Extension: 35
Application memory full.
Contact your local ABB representative.
Extension: Other
Corrupted application file
*Reload application.
If fault is still active, contact your local
ABB representative.
Code
Fault
(fieldbus code)
Cause
What to do
Содержание ACS850 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Страница 4: ......
Страница 56: ...56 Control locations and operating modes ...
Страница 262: ...262 Parameters ...
Страница 310: ...310 Fault tracing ...
Страница 348: ...348 Control through a fieldbus adapter ...
Страница 358: ...358 Drive to drive link ...
Страница 368: ...368 Control chain and drive logic diagrams ...