Parameters 159
15.12
AO2 src min
Defines the real value of the signal (selected by parameter
) that corresponds to the minimum AO1 output
value (defined by parameter
). See
parameter
-32768.000 …
32768.000
Real signal value corresponding to minimum AO2 output
value.
1000 = 1
15.13
AO3 src
Selects a drive signal to be connected to analogue output
AO3.
Speed rpm
(see page
).
1073742081
Speed %
1073742082
Frequency
(see page
1073742083
Current
(see page
).
1073742084
Current %
(see page
).
1073742085
Torque
).
1073742086
Dc-voltage
1073742087
Power inu
(see page
1073742102
Power motor
(see page
).
1073742103
SpRef unramp
(see page
).
1073742595
SpRef ramped
(see page
).
1073742597
SpRef used
(see page
).
1073742598
TorqRef used
1073742606
Process act
(see page
).
1073742851
Proc PID out
(see page
).
1073742853
Pointer
on page
).
-
15.14
AO3 filt time
Defines the filtering time constant for analogue output AO3.
See parameter
.
0.000 … 30.000 s
Filter time constant.
1000 = 1 s
15.15
AO3 out max
Defines the maximum output value for analogue output AO3.
0.000 … 22.700 mA Maximum AO3 output value.
1000 = 1 mA
15.16
AO3 out min
Defines the minimum output value for analogue output AO3.
0.000 … 22.700 mA Minimum AO3 output value.
1000 = 1 mA
No.
Name/Value
Description
FbEq
Содержание ACS850 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Страница 4: ......
Страница 56: ...56 Control locations and operating modes ...
Страница 262: ...262 Parameters ...
Страница 310: ...310 Fault tracing ...
Страница 348: ...348 Control through a fieldbus adapter ...
Страница 358: ...358 Drive to drive link ...
Страница 368: ...368 Control chain and drive logic diagrams ...