Parameters 115
03.12
Torq ref sp lim
Torque reference limited by the rush control (value in
percent). Torque is limited to ensure that the speed is
between the minimum and maximum speed limits defined by
parameters
and
.
10 = 1%
03.13
Torq ref to TC
Torque reference in percent for the torque control.
10 = 1%
03.14
Torq ref used
Torque reference after frequency, voltage and torque limiters.
100% corresponds to the motor nominal torque.
10 = 1%
03.15
Brake torq mem
Torque value (in percent) stored when the mechanical brake
close command is issued.
10 = 1%
03.16
Brake command
Brake on/off command; 0 = close, 1 = open. For brake on/off
control, connect this signal to a relay output (or digital output).
See section
on page
.
1 = 1
03.17
Flux actual
Actual flux reference in percent.
1 = 1%
03.18
Speed ref pot
Output of the motor potentiometer function. (The motor
potentiometer is configured using parameters
.)
100 = 1 rpm
03.20
Max speed ref
Maximum speed reference.
100 = 1 rpm
03.21
Min speed ref
Minimum speed reference.
100 = 1 rpm
04
04 Appl values
Process and counter values.
04.01
Process act1
Process feedback 1 for the process PID controller.
100 = 1 unit
04.02
Process act2
Process feedback 2 for the process PID controller.
100 = 1 unit
04.03
Process act
Final process feedback after process feedback selection and
modification.
100 = 1 unit
04.04
Process PID err
Process PID error, i.e. difference between PID setpoint and
feedback.
10 = 1 unit
04.05
Process PID out
Output of the process PID controller.
10 = 1 unit
04.06
Process var1
Process variable 1. See parameter group
1000 = 1
04.07
Process var2
Process variable 2. See parameter group
1000 = 1
04.08
Process var3
Process variable 3. See parameter group
1000 = 1
04.09
Counter ontime1
Reading of on-time counter 1. See parameter
. Can be reset by entering a 0.
1 = 1 s
04.10
Counter ontime2
Reading of on-time counter 2. See parameter group
. Can be reset by entering a 0.
1 = 1 s
04.11
Counter edge1
Reading of rising edge counter 1. See parameter group
. Can be reset by entering a 0.
1 = 1
04.12
Counter edge2
Reading of rising edge counter 2. See parameter group
. Can be reset by entering a 0.
1 = 1
04.13
Counter value1
Reading of value counter 1. See parameter group
. Can be reset by entering a 0.
1 = 1
04.14
Counter value2
Reading of value counter 2. See parameter group
. Can be reset by entering a 0.
1 = 1
No.
Name/Value
Description
FbEq
Содержание ACS850 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Страница 4: ......
Страница 56: ...56 Control locations and operating modes ...
Страница 262: ...262 Parameters ...
Страница 310: ...310 Fault tracing ...
Страница 348: ...348 Control through a fieldbus adapter ...
Страница 358: ...358 Drive to drive link ...
Страница 368: ...368 Control chain and drive logic diagrams ...