Parameters 141
SpRef ramped
(see page
).
1073742597
SpRef used
(see page
).
1073742598
TorqRef used
(see page
).
1073742606
Process act
(see page
).
1073742851
Proc PID out
(see page
).
1073742853
Pointer
Value pointer setting (see
on page
).
-
15.08
AO2 filt time
Defines the filtering time constant for analogue output AO2.
See parameter
.
0.000 … 30.000 s
Filter time constant.
1000 = 1 s
15.09
AO2 out max
Defines the maximum output value for analogue output AO2.
0.000 … 22.700 mA Maximum AO2 output value.
1000 = 1 mA
15.10
AO2 out min
Defines the minimum output value for analogue output AO2.
0.000 … 22.700 mA Minimum AO2 output value.
1000 = 1 mA
15.11
AO2 src max
Defines the real value of the signal (selected by parameter
) that corresponds to the maximum AO2 output
value (defined by parameter
-32768.000 …
32768.000
Real signal value corresponding to maximum AO2 output
value.
1000 = 1
No.
Name/Value
Description
FbEq
I
AO2
(mA)
Signal
(real)
selected by par.
I
AO2
(mA)
Signal
(real)
selected by par.
Содержание ACS850-04 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Страница 4: ......
Страница 10: ...10 Table of contents...
Страница 52: ...52 The ACS850 control panel...
Страница 56: ...56 Control locations and operating modes...
Страница 80: ...80 Program features...
Страница 236: ...236 Parameters...
Страница 286: ...286 Fieldbus control...
Страница 294: ...294 Control block diagrams...