![ABB ACS850-04 series Скачать руководство пользователя страница 281](http://html1.mh-extra.com/html/abb/acs850-04-series/acs850-04-series_firmware-manual_3365228281.webp)
Fieldbus control 281
Drive control parameters
The Setting for fieldbus control column gives the value to use when the fieldbus
interface is the desired source or destination for that particular signal. The Function/
Information column gives a description of the parameter.
Parameter
Setting for
fieldbus control
Function/Information
CONTROL COMMAND SOURCE SELECTION
(3)
Selects fieldbus as the source for the start
and stop commands when EXT1 is selected
as the active control location.
(3)
Selects fieldbus as the source for the start
and stop commands when EXT2 is selected
as the active control location.
(3)
(4)
Fieldbus reference REF1 or REF2 is used
as speed reference 1.
(3)
(4)
Fieldbus reference REF1 or REF2 is used
as speed reference 2.
(3)
(4)
Fieldbus reference REF1 or REF2 is used
as torque reference 1.
(3)
(4)
Fieldbus reference REF1 or REF2 is used
as torque reference addition.
SYSTEM CONTROL INPUTS
(0)
(1)
Saves parameter value changes (including
those made through fieldbus control) to
permanent memory.
Содержание ACS850-04 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Страница 4: ......
Страница 10: ...10 Table of contents...
Страница 52: ...52 The ACS850 control panel...
Страница 56: ...56 Control locations and operating modes...
Страница 80: ...80 Program features...
Страница 236: ...236 Parameters...
Страница 286: ...286 Fieldbus control...
Страница 294: ...294 Control block diagrams...