274 Fault tracing
0061
SPEED FEEDBACK
(0x8480)
No speed feedback is
received.
Check the settings of the parameters in
group
Check encoder installation. See the
description of fault 0039 (ENCODER1)
for more information.
0062
D2D SLOT COMM
(0x7584)
Drive-to-drive link is set to use
an FSCA module for
communication, but no module
is detected in specified slot.
Check the settings of parameters
and
. Ensure that the FSCA module
has been detected by checking
parameters
Check that the FSCA module is correctly
wired.
Try installing the FSCA module into
another slot. If the problem persists,
contact your local ABB representative.
0063
MOTOR TEMP2
(0x4313)
Programmable fault:
Estimated motor temperature
(based on motor thermal
model) has exceeded fault limit
defined by parameter
Check motor ratings and load.
Let motor cool down. Ensure proper
motor cooling: Check cooling fan, clean
cooling surfaces, etc.
Check value of alarm limit.
Check motor thermal model settings
(parameters
…
Measured motor temperature
has exceeded fault limit
defined by parameter
Check that actual number of sensors
corresponds to value set by parameter
Check motor ratings and load.
Let motor cool down. Ensure proper
motor cooling: Check cooling fan, clean
cooling surfaces, etc.
Check value of alarm limit.
0064
IGBT OVERLOAD
(0x5482)
Excessive IGBT junction to
case temperature. This fault
protects the IGBT(s) and can
be activated by a short circuit
in the motor cable.
Check motor cable.
0065
IGBT TEMP
(0x4210)
Drive IGBT temperature is
excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
0066
COOLING
(0x4290)
Drive module temperature is
excessive.
Check ambient temperature. If it exceeds
40 °C (104 °F), ensure that load current
does not exceed derated load capacity of
drive. See appropriate
Hardware Manual.
Check drive module cooling air flow and
fan operation.
Check inside of cabinet and heatsink of
drive module for dust pick-up. Clean
whenever necessary.
0201
T2 OVERLOAD
(0x0201)
Firmware time level 2 overload
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0202
T3 OVERLOAD
(0x6100)
Firmware time level 3 overload
Note:
This fault cannot be
reset.
Contact your local ABB representative.
Code
Fault
(fieldbus code)
Cause
What to do
Содержание ACS850-04 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Страница 4: ......
Страница 10: ...10 Table of contents...
Страница 52: ...52 The ACS850 control panel...
Страница 56: ...56 Control locations and operating modes...
Страница 80: ...80 Program features...
Страница 236: ...236 Parameters...
Страница 286: ...286 Fieldbus control...
Страница 294: ...294 Control block diagrams...