230 Parameters
95.03
Temp inu ambient
Defines the maximum ambient temperature. The value is
used by the drive cooling diagnostics.
0 … 55 °C
Drive ambient temperature.
1 = 1 °C
97
97 User motor par
Motor values supplied by the user that are used in the motor
model.
97.01
Use given params
Activates the motor model parameters
and the
rotor angle offset parameter
Notes
:
• Parameter value is automatically set to zero when ID run is
selected by parameter
. The values of
are updated according to the
motor characteristics identified during the ID run.
• This parameter cannot be changed while the drive is
running.
NoUserPars
Parameters
inactive.
0
UserMotPars
are used in the motor
model.
1
UserPosOffs
The value of parameter
are inactive.
2
AllUserPars
are used in the motor
model, and the value of parameter
is used as the rotor
angle offset.
3
97.02
Rs user
Defines the stator resistance
R
S
of the motor model.
0.00000 … 0.50000
p.u.
Stator resistance in per unit.
100000 =
1 p.u.
97.03
Rr user
Defines the rotor resistance
R
R
of the motor model.
Note:
This parameter is valid only for asynchronous motors.
0.00000 … 0.50000
p.u.
Rotor resistance in per unit.
100000 =
1 p.u.
97.04
Lm user
Defines the main inductance
L
M
of the motor model.
Note:
This parameter is valid only for asynchronous motors.
0.00000 …
10.00000 p.u.
Main inductance in per unit.
100000 =
1 p.u.
97.05
SigmaL user
Defines the leakage inductance
σ
L
S
.
Note:
This parameter is valid only for asynchronous motors.
0.00000 … 1.00000
p.u.
Leakage inductance in per unit.
100000 =
1 p.u.
97.06
Ld user
Defines the direct axis (synchronous) inductance.
Note:
This parameter is valid only for permanent magnet
motors.
0.00000 …
10.00000 p.u
Direct axis inductance in per unit.
100000 =
1 p.u.
97.07
Lq user
Defines the quadrature axis (synchronous) inductance.
Note:
This parameter is valid only for permanent magnet
motors.
0.00000 …
10.00000 p.u
Quadrature axis inductance in per unit.
100000 =
1 p.u.
No.
Name/Value
Description
FbEq
Содержание ACS850-04 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Страница 4: ......
Страница 10: ...10 Table of contents...
Страница 52: ...52 The ACS850 control panel...
Страница 56: ...56 Control locations and operating modes...
Страница 80: ...80 Program features...
Страница 236: ...236 Parameters...
Страница 286: ...286 Fieldbus control...
Страница 294: ...294 Control block diagrams...