Parameters 115
10.17
Start enable
Selects the source for the start enable signal.
1 = Start enable.
If the signal is switched off, the drive will not start or coasts to
stop if running.
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
DI6
Digital input DI6 (as indicated by
, bit 5).
1074070017
DIO4
Digital input/output DIO4 (as indicated by
,
bit 3).
1073938947
DIO5
Digital input/output DIO5 (as indicated by
,
bit 4).
1074004483
DIO6
Digital input/output DIO6 (as indicated by
,
bit 5).
1074070019
Const
Bit pointer setting (see
on page
). -
Pointer
10.19
Start inhibit
Enables the start inhibit function. The function prevents drive
restart (i.e. protects against unexpected start) if
• the drive trips on a fault and the fault is reset,
• the run enable signal is activated while the start command is
active (see parameter
),
• control changes from local to remote, or
• external control switches from EXT1 to EXT2 or vice versa.
An active start inhibit can be reset with a stop command.
Note that in certain applications it is necessary to allow the
drive to restart.
Disabled
The start inhibit function is disabled.
0
Enabled
The start inhibit function is enabled.
1
10.20
Start interl func
Defines how the start interlock input (DIIL) on the JCU control
unit affects the drive operation.
Off2 stop
With the drive running:
• 1 = Normal operation.
• 0 = Stop by coasting. The drive can be restarted by
restoring the start interlock signal and switching the start
signal from 0 to 1.
With the drive stopped:
• 1 = Starting allowed.
• 0 = Starting not allowed.
0
Off3 stop
With the drive running:
• 1 = Normal operation.
• 0 = Stop by ramping. The deceleration time is defined by
parameter
. The drive can be restarted
by restoring the start interlock signal and switching the
start signal from 0 to 1.
With the drive stopped:
• 1 = Starting allowed.
• 0 = Starting not allowed.
1
No.
Name/Value
Description
FbEq
Содержание ACS850-04 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Страница 4: ......
Страница 10: ...10 Table of contents...
Страница 52: ...52 The ACS850 control panel...
Страница 56: ...56 Control locations and operating modes...
Страница 80: ...80 Program features...
Страница 236: ...236 Parameters...
Страница 286: ...286 Fieldbus control...
Страница 294: ...294 Control block diagrams...