Parameters 113
DI6
Digital input DI6 (as indicated by
, bit 5).
1074070017
DIO4
Digital input/output DIO4 (as indicated by
,
bit 3).
1073938947
DIO5
Digital input/output DIO5 (as indicated by
,
bit 4).
1074004483
DIO6
Digital input/output DIO6 (as indicated by
,
bit 5).
1074070019
Const
Bit pointer setting (see
on page
). -
Pointer
10.10
Fault reset sel
Selects the source of the external fault reset signal. The
signal resets the drive after a fault trip if the cause of the fault
no longer exists.
0 -> 1 = Fault reset.
Note:
A fault reset from the fieldbus is always observed
regardless of this setting.
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
DI6
Digital input DI6 (as indicated by
, bit 5).
1074070017
DIO4
Digital input/output DIO4 (as indicated by
,
bit 3).
1073938947
DIO5
Digital input/output DIO5 (as indicated by
,
bit 4).
1074004483
DIO6
Digital input/output DIO6 (as indicated by
,
bit 5).
1074070019
Const
Bit pointer setting (see
on page
). -
Pointer
10.11
Run enable
Selects the source of the external run enable signal. If the run
enable signal is switched off, the drive will not start, or coasts
to stop if running.
1 = Run enable.
Note:
This parameter cannot be changed while the drive is
running.
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
DI6
Digital input DI6 (as indicated by
, bit 5).
1074070017
DIO4
Digital input/output DIO4 (as indicated by
,
bit 3).
1073938947
DIO5
Digital input/output DIO5 (as indicated by
,
bit 4).
1074004483
DIO6
Digital input/output DIO6 (as indicated by
,
bit 5).
1074070019
No.
Name/Value
Description
FbEq
Содержание ACS850-04 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Страница 4: ......
Страница 10: ...10 Table of contents...
Страница 52: ...52 The ACS850 control panel...
Страница 56: ...56 Control locations and operating modes...
Страница 80: ...80 Program features...
Страница 236: ...236 Parameters...
Страница 286: ...286 Fieldbus control...
Страница 294: ...294 Control block diagrams...