182 Parameters
31.14
Mot therm time
Defines the thermal time constant for the motor thermal
protection model (i.e. time inside which the temperature has
reached 63% of the nominal temperature). See the motor
manufacturer's recommendations.
The motor thermal protection model is used when parameter
.
100 … 10000 s
Motor thermal time constant.
1 = 1 s
32
32 Automatic reset
Defines conditions for automatic fault resets.
32.01
Autoreset sel
Selects faults that are automatically reset. The parameter is a
16-bit word with each bit corresponding to a fault type.
Whenever a bit is set to 1, the corresponding fault is
automatically reset.
The bits of the binary number correspond to the following
faults:
32.02
Number of trials
Defines the number of automatic fault resets the drive
performs within the time defined by parameter
0 … 5
Number of automatic resets.
1 = 1
32.03
Trial time
Defines the time for the automatic fault reset function. See
parameter
1.0 … 600.0 s
Time for automatic resets.
10 = 1 s
No.
Name/Value
Description
FbEq
100%
63%
100%
Time
Time
Motor thermal time
Motor load
Temperature rise
Bit
Fault
0
Overcurrent
1
Overvoltage
2
Undervoltage
3
AI min
4
Line converter
5
External fault
Содержание ACS850-04 series
Страница 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Страница 4: ......
Страница 10: ...10 Table of contents...
Страница 52: ...52 The ACS850 control panel...
Страница 56: ...56 Control locations and operating modes...
Страница 80: ...80 Program features...
Страница 236: ...236 Parameters...
Страница 286: ...286 Fieldbus control...
Страница 294: ...294 Control block diagrams...