ACS550 User’s Manual
Diagnostics
2013
(Note 1)
AUTORESET
This alarm warns that the drive is about to perform an automatic fault
reset, which may start the motor.
• To control automatic reset, use
.
2014
(Note 1)
AUTOCHANGE
This alarm warns that the PFC autochange function is active.
• To control PFC, use
and the
on page
.
2015
PFC
I
LOCK
This alarm warns that the PFC interlocks are active, which means that
the drive cannot start the following:
• Any motor (when Autochange is used).
• The speed regulated motor (when Autochange is not used).
2016/
2017
RESERVED
Not used.
2018
(Note 1)
PID
SLEEP
This alarm warns that the PID sleep function is active, which means
that the motor could accelerate when the PID sleep function ends.
• To control PID sleep, use parameters 4022…4026 or 4122…4126.
2019
ID
RUN
Performing ID Run.
2020
RESERVED
Not used.
2021
START
ENABLE
1
MISSING
This alarm warns that the Start Enable 1 signal is missing.
• To control Start Enable 1 function, use parameter 1608.
To correct, check:
• Digital input configuration.
• Communication settings.
2022
START
ENABLE
2
MISSING
This alarm warns that the Start Enable 2 signal is missing.
• To control Start Enable 2 function, use parameter 1609.
To correct, check:
• Digital input configuration.
• Communication settings.
2023
EMERGENCY
STOP
Emergency stop activated.
2024
ENCODER
ERROR
The drive is not detecting a valid encoder signal. Check for and
correct:
• Encoder presence and proper connection (reverse wired, loose
connection,or short circuit).
• Voltage logic levels are outside of the specified range.
• A working and properly connected Pulse Encoder Interface Module,
OTAC-01.
• Wrong value entered in parameter 5001
PULSE
NR
. A wrong value
will only be detected if the error is such that the calculated slip is
greater than 4 times the rated slip of the motor.
• Encoder is not being used, but parameter 5002
ENCODER
ENABLE
=
1 (
ENABLE
).
2025
FIRST
START
Signals that a the drive is performing a First Start evaluation of motor
characteristics. This is normal the first time the motor is run after motor
parameters are entered or changed. See parameter 9910
ID
RUN
for a
description of motor models.
2026
RESERVED
Not used.
Alarm
code
Display
Description
Содержание ACS550 Series
Страница 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 User s Manual Table of contents ...
Страница 84: ...84 ACS550 User s Manual Application macros ...
Страница 188: ...188 ACS550 User s Manual Parameters ...
Страница 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Страница 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...
Страница 296: ...296 ACS550 User s Manual Technical data ...