![ABB ACS550 Series Скачать руководство пользователя страница 88](http://html.mh-extra.com/html/abb/acs550-series/acs550-series_user-manual_334088.webp)
88
ACS550 User’s Manual
Parameters
1206
CONST
SPEED
5
0…30000 rpm / 0.0…500.0 Hz
1 rpm / 0.1 Hz 01: 1500 rpm / 25.0 Hz
U1: 1800 rpm / 30.0 Hz
1207
CONST
SPEED
6
0…30000 rpm / 0.0…500.0 Hz
1 rpm / 0.1 Hz 01: 2400 rpm / 40.0 Hz
U1: 2880 rpm / 48.0 Hz
1208
CONST
SPEED
7
0…30000 rpm / 0.0…500.0 Hz
1 rpm / 0.1 Hz 01: 3000 rpm / 50.0 Hz
U1: 3600 rpm / 60.0 Hz
1209
TIMED
MODE
SEL
1 =
EXT
/
CS
1/2/3, 2 =
CS
1/2/3/4
1
2 (
CS
1/2/3/4)
!
Group 13: ANALOG INPUTS
1301
MINIMUM
AI
1 0.0…100.0%
0.1%
0.0%
1302
MAXIMUM
AI
1 0.0…100.0%
0.1%
100.0%
1303
FILTER
AI
1 0.0…10.0 s
0.1 s
0.1 s
1304
MINIMUM
AI
2 0.0…100.0%
0.1%
0.0%
1305
MAXIMUM
AI
2 0.0…100.0%
0.1%
100.0%
1306
FILTER
AI
2 0.0…10.0 s
0.1 s
0.1 s
Group 14: RELAY OUTPUTS
1401
RELAY
OUTPUT
1
0…47, 52
1
1 (
READY
)
1402
RELAY
OUTPUT
2
0…47, 52
1
2 (
RUN
)
1403
RELAY
OUTPUT
3
0…47, 52
1
3 [
FAULT
(-1)]
1404
RO
1
ON
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1405
RO
1
OFF
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1406
RO
2
ON
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1407
RO
2
OFF
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1408
RO
3
ON
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1409
RO
3
OFF
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1410
RELAY
OUTPUT
4
0…46, 52
1
0 (
NOT
SEL
)
1411
RELAY
OUTPUT
5
0…46, 52
1
0 (
NOT
SEL
)
1412
RELAY
OUTPUT
6
0…46, 52
1
0 (
NOT
SEL
)
1413
RO
4
ON
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1414
RO
4
OFF
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1415
RO
5
ON
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1416
RO
5
OFF
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1417
RO
6
ON
DELAY
0.0…3600.0 s
0.1 s
0.0 s
1418
RO
6
OFF
DELAY
0.0…3600.0 s
0.1 s
0.0 s
Group 15: ANALOG OUTPUTS
1501
AO
1
CONTENT
SEL
99…159
1
103 (parameter 0103
OUTPUT
FREQ
)
1502
AO
1
CONTENT
MIN
-
-
Defined by par. 0103
1503
AO
1
CONTENT
MAX
-
-
Defined by par. 0103
1504
MINIMUM
AO
1
0.0…20.0 mA
0.1 mA
0.0 mA
1505
MAXIMUM
AO
1
0.0…20.0 mA
0.1 mA
20.0 mA
1506
FILTER
AO
1
0.0…10.0 s
0.1 s
0.1 s
1507
AO
2
CONTENT
SEL
99…159
1
104 (parameter 0104
CURRENT
)
1508
AO
2
CONTENT
MIN
-
-
Defined by par. 0104
1509
AO
2
CONTENT
MAX
-
-
Defined by par. 0104
1510
MINIMUM
AO
2
0.0…20.0 mA
0.1 mA
0.0 mA
Code
Name
Range
Resolution
Default
User S
Содержание ACS550 Series
Страница 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 User s Manual Table of contents ...
Страница 84: ...84 ACS550 User s Manual Application macros ...
Страница 188: ...188 ACS550 User s Manual Parameters ...
Страница 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Страница 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...
Страница 296: ...296 ACS550 User s Manual Technical data ...