![ABB ACS550 Series Скачать руководство пользователя страница 265](http://html.mh-extra.com/html/abb/acs550-series/acs550-series_user-manual_334265.webp)
ACS550 User’s Manual
265
Technical data
Fuses, 500…600 V drives
Emergency stop devices
The overall design of the installation must include emergency stop devices and any
other safety equipment that may be needed. Pressing STOP on the drive’s control
panel does NOT:
• generate an emergency stop of the motor
• separate the drive from dangerous potential.
Input power cables/wiring
Input wiring can be any of:
• a four conductor cable (three phases and ground/protective earth). Shielding is
not required.
• four insulated conductors routed through conduit.
-124A-4
124
160
175
JJS-175
-125A-4
125
-157A-4
157
200
200
JJS-200
-180A-4
180
250
250
JJS-250
-195A-4
195
-246A-4
245
350
JJS-350
00467918.xls B
ACS550-U1-
see below
Input current
A
Input power (mains) fuses
IEC 269 gG (A) UL Class T (A)
Bussmann type
-02A7-6
2.7
10
10
JJS-10
-03A9-6
3.9
-06A1-6
6.1
-09A0-6
9.0
16
15
JJS-15
-011A-6
11.0
-017A-6
17.0
25
25
JJS-25
-022A-6
22.0
-027A-6
27
35
40
JJS-40
-032A-6
32
-041A-6
41
50
50
JJS-50
-052A-6
52
60
60
JJS-60
-062A-6
62
80
80
JJS-80
-077A-6
77
100
JJS-100
-099A-6
99
125
150
JJS-150
-125A-6
125
160
175
JJS-175
-144A-6
144
200
200
JJS-200
00467918.xls B
ACS550-x1-
see below
Input current
A
Input power (mains) fuses
IEC 269 gG (A)
UL Class T (A)
Bussmann type
Содержание ACS550 Series
Страница 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 User s Manual Table of contents ...
Страница 84: ...84 ACS550 User s Manual Application macros ...
Страница 188: ...188 ACS550 User s Manual Parameters ...
Страница 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Страница 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...
Страница 296: ...296 ACS550 User s Manual Technical data ...