90
ACS550 User’s Manual
Parameters
Group 22: ACCEL/DECEL
2201
ACC
/
DEC
1/2
SEL
-6…7
1
5 (
DI
5)
2202
ACCELER
TIME
1
0.0…1800.0 s
0.1 s
5.0 s
2203
DECELER
TIME
1
0.0…1800.0 s
0.1 s
5.0 s
2204
RAMP
SHAPE
1
0.0 =
LINEAR
, 0.1…1000.0 s
0.1 s
0.0 s
2205
ACCELER
TIME
2
0.0…1800.0 s
0.1 s
60.0 s
2206
DECELER
TIME
2
0.0…1800.0 s
0.1 s
60.0 s
2207
RAMP
SHAPE
2
0.0 =
LINEAR
, 0.1…1000.0 s
0.1 s
0.0 s
2208
EMERG
DEC
TIME
0.0…1800.0 s
0.1 s
1.0 s
2209
RAMP
INPUT
0
-6…7
1
0 (
NOT
SEL
)
Group 23: SPEED CONTROL
2301
PROP
GAIN
0.00…200.00
0.01
10.00
2302
INTEGRATION
TIME
0.00…600.00 s
0.01 s
2.50 s
2303
DERIVATION
TIME
0…10000 ms
1 ms
0 ms
2304
ACC
COMPENSATION
0.00…600.00 s
0.01 s
0.00 s
2305
AUTOTUNE
RUN
0 =
OFF
, 1 =
ON
1
0 (
OFF
)
Group 24: TORQUE CONTROL
2401
TORQ
RAMP
UP
0.00…120.00 s
0.01 s
0.00 s
2402
TORQ
RAMP
DOWN
0.00…120.00 s 0.01 s
0.00 s
Group 25: CRITICAL SPEEDS
2501
CRIT
SPEED
SEL
0 =
OFF
, 1 =
ON
1
0 (
OFF
)
2502
CRIT
SPEED
1
LO
0…30000 rpm / 0.0…500.0 Hz
1 rpm / 0.1 Hz 0 rpm / 0.0 Hz
2503
CRIT
SPEED
1
HI
0…30000 rpm / 0.0…500.0 Hz
1 rpm / 0.1 Hz 0 rpm / 0.0 Hz
2504
CRIT
SPEED
2
LO
0…30000 rpm / 0.0…500.0 Hz
1 rpm / 0.1 Hz 0 rpm / 0.0 Hz
2505
CRIT
SPEED
2
HI
0…30000 rpm / 0.0…500.0 Hz
1 rpm / 0.1 Hz 0 rpm / 0.0 Hz
2506
CRIT
SPEED
3
LO
0…30000 rpm / 0.0…500.0 Hz
1 rpm / 0.1 Hz 0 rpm / 0.0 Hz
2507
CRIT
SPEED
3
HI
0…30000 rpm / 0.0…500.0 Hz
1 rpm / 0.1 Hz 0 rpm / 0.0 Hz
Group 26: MOTOR CONTROL
2601
FLUX
OPT
ENABLE
0 =
OFF
, 1 =
ON
1
0 (
OFF
)
2602
FLUX
BRAKING
0 =
OFF
, 1 =
ON
1
0 (
OFF
)
2603
IR
COMP
VOLT
0.0…100.0 V
0.1 V
Size dependent
2604
IR
COMP
FREQ
0…100%
1%
80%
2605
U
/
F
RATIO
1 =
LINEAR
, 2 =
SQUARED
1
1 (
LINEAR
)
2606
SWITCHING
FREQ
1, 4, 8, 12 kHz
-
4 kHz
2607
SWITCH
FREQ
CTRL
0 =
OFF
, 1 =
ON
1
1 (
ON
)
2608
SLIP
COMP
RATIO
0…200%
1%
0
2609
NOISE
SMOOTHING
0 =
DISABLE
, 1 =
ENABLE
1
0 (
DISABLE
)
2619
DC
STABILIZER
0 =
DISABLE
, 1 =
ENABLE
1
0 (
DISABLE
)
Group 29: MAINTENANCE TRIG
2901
COOLING
FAN
TRIG
0.0…6553.5 kh, 0.0 disables
0.1 kh
0.0 kh
2902
COOLING
FAN
ACT
0.0…6553.5 kh
0.1 kh
0.0 kh
2903
REVOLUTION
TRIG
0…65535 Mrev, 0 disables
1 Mrev
0 Mrev
2904
REVOLUTION
ACT
0…65535 Mrev
1 Mrev
0 Mrev
2905
RUN
TIME
TRIG
0.0…6553.5 kh, 0.0 disables
0.1 kh
0.0 kh
2906
RUN
TIME
ACT
0.0…6553.5 kh
0.1 kh
0.0 kh
Code
Name
Range
Resolution
Default
User S
Содержание ACS550 Series
Страница 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 User s Manual Table of contents ...
Страница 84: ...84 ACS550 User s Manual Application macros ...
Страница 188: ...188 ACS550 User s Manual Parameters ...
Страница 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Страница 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...
Страница 296: ...296 ACS550 User s Manual Technical data ...