![ABB ACS550 Series Скачать руководство пользователя страница 183](http://html.mh-extra.com/html/abb/acs550-series/acs550-series_user-manual_334183.webp)
ACS550 User’s Manual
183
3 =
DI
3 – Enables the Interlocks function and assigns a digital input (starting with
DI
3) to the interlock signal for each
PFC relay. These assignments are defined in the following table and depend on:
• the number of PFC relays [number of parameters 1401…1403 and 1410…1412 with value = 31 (
PFC
)]
• the Autochange function status (disabled if 8118
AUTOCHNG
INTERV
= 0, and otherwise enabled).
4 =
DI
4 – Enables the Interlock function and assigns a digital input (starting with
DI
4) to the interlock signal for each
PFC relay. These assignments are defined in the following table and depend on:
• the number of PFC relays [number of parameters 1401…1403 and 1410…1412 with value = 31 (
PFC
)]
• the Autochange function status (disabled if 8118
AUTOCHNG
INTERV
= 0, and otherwise enabled).
Code Description
No. PFC
relays
Autochange disabled
(P 8118)
Autochange enabled
(P 8118)
0
DI
1…
DI
2: Free
DI
3: Speed Reg Motor
DI
4…
DI
6: Free
Not allowed
1
DI
1…
DI
2: Free
DI
3: Speed Reg Motor
DI
4: First PFC Relay
DI
5…
DI
6: Free
DI
1…
DI
2: Free
DI
3: First PFC Relay
DI
4…
DI
6: Free
2
DI
1…
DI
2: Free
DI
3: Speed Reg Motor
DI
4: First PFC Relay
DI
5: Second PFC Relay
DI
6: Free
DI
1…
DI
2: Free
DI
3: First PFC Relay
DI
4: Second PFC Relay
DI
5…
DI
6: Free
3
DI
1…
DI
2: Free
DI
3: Speed Reg Motor
DI
4: First PFC Relay
DI
5: Second PFC Relay
DI
6: Third PFC Relay
DI
1…
DI
2: Free
DI
3: First PFC Relay
DI
4: Second PFC Relay
DI
5: Third PFC Relay
DI
6: Free
4
Not allowed
DI
1…
DI
2: Free
DI
3: First PFC Relay
DI
4: Second PFC Relay
DI
5: Third PFC Relay
DI
6: Fourth PFC Relay
5…6
Not allowed
Not allowed
No. PFC
relays
Autochange disabled
(P 8118)
Autochange enabled
(P 8118)
0
DI
1…
DI
3: Free
DI
4: Speed Reg Motor
DI
5…
DI
6: Free
Not allowed
1
DI
1…
DI
3: Free
DI
4: Speed Reg Motor
DI
5: First PFC Relay
DI
6: Free
DI
1…
DI
3: Free
DI
4: First PFC Relay
DI
5…
DI
6: Free
2
DI
1…
DI
3: Free
DI
4: Speed Reg Motor
DI
5: First PFC Relay
DI
6: Second PFC Relay
DI
1…
DI
3: Free
DI
4: First PFC Relay
DI
5: Second PFC Relay
DI
6: Free
3
Not allowed
DI
1…
DI
3: Free
DI
4: First PFC Relay
DI
5: Second PFC Relay
DI
6: Third PFC Relay
4…6
Not allowed
Not allowed
Содержание ACS550 Series
Страница 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 User s Manual Table of contents ...
Страница 84: ...84 ACS550 User s Manual Application macros ...
Страница 188: ...188 ACS550 User s Manual Parameters ...
Страница 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Страница 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...
Страница 296: ...296 ACS550 User s Manual Technical data ...