![ABB ACS550 Series Скачать руководство пользователя страница 26](http://html.mh-extra.com/html/abb/acs550-series/acs550-series_user-manual_334026.webp)
26
ACS550 User’s Manual
Installation
Wiring
IP21
/ UL type 1 enclosure with
conduit
1. Open the appropriate knockouts in the conduit/gland
box. (See section
on page
2. Install thin-wall conduit clamps (not supplied).
3. Install conduit/gland box.
4. Connect conduit runs to box.
5. Route input power and motor wiring through conduits
(must be separate conduit runs).
6. Strip wires.
7. Connect power, motor and ground wires to the drive
terminals.
Note:
For R5 frame size, the minimum power cable
size is 25 mm
2
(4 AWG).
For R6 frame size, refer to section
Power terminal considerations – R6 frame size
on
page
8. Route the control cable through the conduit (must be
separate from input power and motor conduit runs).
9. Strip the control cable sheathing and twist the copper
screen into a pig-tail.
10. Connect the ground screen pig-tail for digital and
analog I/O cables at X1-1. (Ground only at drive end.)
11. Connect the ground screen pig-tail for RS485 cables
at X1-28 or X1-32. (Ground only at drive end.)
12. Strip and connect the individual control wires to the
13. Install the conduit/gland box cover (1 screw).
2
X0007
3
X0005
4
IP2004
7
7
5
10
8
IP2005
12
Содержание ACS550 Series
Страница 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 User s Manual Table of contents ...
Страница 84: ...84 ACS550 User s Manual Application macros ...
Страница 188: ...188 ACS550 User s Manual Parameters ...
Страница 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Страница 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...
Страница 296: ...296 ACS550 User s Manual Technical data ...