![ABB ACS550 Series Скачать руководство пользователя страница 106](http://html.mh-extra.com/html/abb/acs550-series/acs550-series_user-manual_334106.webp)
106
ACS550 User’s Manual
Group 04: FAULT HISTORY
This group stores a recent history of the faults reported by the drive.
Code Description
0401
LAST FAULT
0 – Clear the fault history (on panel = NO RECORD).
n – Fault code of the last recorded fault. The fault code is displayed as a name. See section
on page
for the fault codes and names. The fault name shown for this parameter may be shorter than the corresponding
name in the fault listing, which shows the names as they are shown in the fault display.
0402
FAULT TIME 1
The day on which the last fault occurred. Either as:
• A date – if real time clock is operating.
• The number of days after power on – if real time clock is not used, or was not set.
0403
FAULT TIME 2
The time at which the last fault occurred. Either as:
• Real time, in format hh:mm:ss – if real time clock is operating.
• The time since power on (minus the whole days reported in 0402), in format hh:mm:ss – if real time clock is not
used, or was not set.
• Format on the Basic Control Panel: The time since power on in 2-second ticks (minus the whole days reported in
0402). 30 ticks = 60 seconds. E.g. Value 514 equals 17 minutes and 8 seconds (= 514/30).
0404
SPEED AT FLT
The motor speed (rpm) at the time the last fault occurred.
0405
FREQ AT FLT
The frequency (Hz) at the time the last fault occurred.
0406
VOLTAGE AT FLT
The DC bus voltage (V) at the time the last fault occurred.
0407
CURRENT AT FLT
The motor current (A) at the time the last fault occurred.
0408
TORQUE AT FLT
The motor torque (%) at the time the last fault occurred.
0409
STATUS AT FLT
The drive status (hex code word) at the time the last fault occurred.
0410
DI 1-3 AT FLT
The status of digital inputs 1…3 at the time the last fault occurred.
0411
DI 4-6 AT FLT
The status of digital inputs 4…6 at the time the last fault occurred.
0412
PREVIOUS FAULT 1
Fault code of the second last fault. Read-only.
0413
PREVIOUS FAULT 2
Fault code of the third last fault. Read-only.
Содержание ACS550 Series
Страница 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 User s Manual Table of contents ...
Страница 84: ...84 ACS550 User s Manual Application macros ...
Страница 188: ...188 ACS550 User s Manual Parameters ...
Страница 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Страница 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...
Страница 296: ...296 ACS550 User s Manual Technical data ...