1209
TIMED MODE SEL
Defines timed function activated, constant speed mode. Timed function can be used to change between external
reference and a maximum of three constant speeds, or to change between a maximum of 4 selectable speeds, i.e.
constant speeds 1, 2, 3 and 4.
1 =
EXT
/
CS
1/2/3 – Selects an external speed when no timed function is active, selects Constant speed 1 when only
Timed function 1 is active, Selects Constant speed 2 when only Timed function 2 is active and selects Constant
speed 3 when both Timed functions 1 and 2 are active.
2 =
CS
1/2/3/4 – Selects Constant speed 1 when no timer is active, selects Constant speed 2 when only Timed
function 1 is active, selects Constant speed 3 when only Timed function 2 is active, selects Constant speed 4 when
both Timed functions are active.
Code Description
TIMER
1
TIMER
2
Function
0
0
External reference
1
0
Constant speed 1 (1202)
0
1
Constant speed 2 (1203)
1
1
Constant speed 3 (1204)
TIMER
1
TIMER
2
Function
0
0
Constant speed 1 (1202)
1
0
Constant speed 2 (1203)
0
1
Constant speed 3 (1204)
1
1
Constant speed 4 (1205)
Содержание ACS550 Series
Страница 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 User s Manual Table of contents ...
Страница 84: ...84 ACS550 User s Manual Application macros ...
Страница 188: ...188 ACS550 User s Manual Parameters ...
Страница 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Страница 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...
Страница 296: ...296 ACS550 User s Manual Technical data ...