ACS550 User’s Manual
251
Diagnostics
2004
DIR
LOCK
The change in direction being attempted is not allowed. Either:
• Do not attempt to change the direction of motor rotation, or
• Change parameter 1003
DIRECTION
to allow direction change (if
reverse operation is safe).
2005
IO
COMM
Fieldbus communication has timed out. Check for and correct:
• Fault setup (3018
COMM
FAULT
FUNC
and 3019
COMM
FAULT
TIME
).
• Communication settings (
or
as appropriate).
• Poor connections and/or noise on line.
2006
AI
1
LOSS
Analog input 1 is lost, or value is less than the minimum setting.
Check:
• Input source and connections.
• Parameter that sets the minimum (3021).
• Parameter that sets the alarm/fault operation (3001),
2007
AI
2
LOSS
Analog input 2 is lost, or value is less than the minimum setting.
Check:
• Input source and connections.
• Parameter that sets the minimum (3022).
• Parameter that sets the alarm/fault operation (3001).
2008
PANEL
LOSS
Panel communication is lost and either:
• Drive is in local control mode (the control panel displays LOC), or
• Drive is in remote control mode (REM) and is parameterized to
accept start/stop, direction or reference from the control panel.
To correct check:
• Communication lines and connections.
• Parameter 3002
PANEL
COMM
ERR
.
• Parameters in
(if drive operation is REM).
2009
DEVICE
OVERTEMP
Drive heatsink is hot. This alarm warns that a
DEVICE
OVERTEMP
fault
may be near.
R1…R4 & R7/R8: 100 °C (212 °F)
R5/R6: 110 °C (230 °F)
Check for and correct:
• Fan failure.
• Obstructions in the air flow.
• Dirt or dust coating on the heat sink.
• Excessive ambient temperature.
• Excessive motor load.
2010
MOTOR
TEMP
Motor is hot, based on either the drive’s estimate or on temperature
feedback. This alarm warns that a
MOT
OVERTEMP
fault trip may be
near. Check:
• Check for overloaded motor.
• Adjust the parameters used for the estimate (3005…3009).
• Check the temperature sensors and
2011
RESERVED
Not used.
2012
MOTOR
STALL
Motor is operating in the stall region. This alarm warns that a
MOTOR
STALL
fault trip may be near.
Alarm
code
Display
Description
Содержание ACS550 Series
Страница 1: ...ACS550 User s Manual ACS550 01 Drives 0 75 132 kW ACS550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 User s Manual Table of contents ...
Страница 84: ...84 ACS550 User s Manual Application macros ...
Страница 188: ...188 ACS550 User s Manual Parameters ...
Страница 242: ...242 ACS550 User s Manual Fieldbus adapter ...
Страница 276: ...276 ACS550 User s Manual Technical data WARNING Do not use RFI EMC filters on IT systems ...
Страница 296: ...296 ACS550 User s Manual Technical data ...